| 2018-01-30 11:16:23 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | 1) LIGHT-FRAME TRUSS-TYPE FLOOR AND ROOF SIGN IS |
| | REQUIRED BY FLORIDA STATUTE. |
| | |
| | THE TYPE OF DESIGN YOU HAVE INDICATED IS INCLUDED AS |
| | LIGHTWEIGHT FLOOR AND ROOF. |
| | |
| | 633.222?BUILDINGS WITH LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION; NOTICE REQUIREMENTS; ENFORCEMENT.? |
| | (1)?THE OWNER OF ANY COMMERCIAL OR INDUSTRIAL |
| | STRUCTURE, OR ANY MULTIUNIT RESIDENTIAL STRUCTURE OF |
| | THREE UNITS OR MORE, THAT USES LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION SHALL MARK THE STRUCTURE WITH A SIGN OR |
| | SYMBOL APPROVED BY THE STATE FIRE MARSHAL IN A MANNER |
| | SUFFICIENT TO WARN PERSONS CONDUCTING FIRE CONTROL AND |
| | OTHER EMERGENCY OPERATIONS OF THE EXISTENCE OF |
| | LIGHT-FRAME TRUSS-TYPE CONSTRUCTION IN THE STRUCTURE. |
| | |
| | (2)?THE STATE FIRE MARSHAL SHALL ADOPT RULES NECESSARY |
| | TO IMPLEMENT THE PROVISIONS OF THIS SECTION, INCLUDING, |
| | BUT NOT LIMITED TO: |
| | (A)?THE DIMENSIONS AND COLOR OF SUCH SIGN OR SYMBOL. |
| | |
| | (B)?THE TIME WITHIN WHICH COMMERCIAL, INDUSTRIAL, AND |
| | MULTIUNIT RESIDENTIAL STRUCTURES THAT USE LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION SHALL BE MARKED AS REQUIRED BY |
| | THIS SECTION. |
| | |
| | (C)?THE LOCATION ON EACH COMMERCIAL, INDUSTRIAL, AND |
| | MULTIUNIT RESIDENTIAL STRUCTURE THAT USES LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION WHERE SUCH SIGN OR SYMBOL MUST |
| | BE POSTED. |
| | |
| | (3)?THE STATE FIRE MARSHAL, AND LOCAL FIRE OFFICIALS IN |
| | ACCORDANCE WITH S. 633.118, SHALL ENFORCE THIS SECTION. |
| | AN OWNER WHO FAILS TO COMPLY WITH THE REQUIREMENTS OF |
| | THIS SECTION IS SUBJECT TO PENALTIES AS PROVIDED IN S. |
| | 633.228. |
| | |
| | |
| | 69A-60.0081 NOTICE REQUIRED FOR STRUCTURES WITH |
| | LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | (1) PURPOSE: THE PURPOSE OF THIS RULE IS TO REQUIRE THE |
| | PLACEMENT OF AN IDENTIFYING SYMBOL ON STRUCTURES |
| | CONSTRUCTED WITH A LIGHT-FRAME TRUSS COMPONENT IN A |
| | MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE |
| | CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE |
| | OF LIGHT-FRAME TRUSS-TYPE CONSTRUCTION IN THE |
| | STRUCTURE. |
| | (2) DEFINITIONS. |
| | (A) ?LIGHT-FRAME TRUSS-TYPE CONSTRUCTION? MEANS A TYPE |
| | OF CONSTRUCTION WHOSE PRIMARY STRUCTURAL ELEMENTS ARE |
| | FORMED BY A SYSTEM OF REPETITIVE WOOD OR LIGHT GAUGE |
| | STEEL FRAMING MEMBERS. |
| | (B) ?APPROVED SYMBOL? MEANS A MALTESE CROSS MEASURING 8 |
| | INCHES HORIZONTALLY AND 8 INCHES VERTICALLY, OF A |
| | BRIGHT RED REFLECTIVE COLOR, DESIGNED IN ACCORDANCE |
| | WITH FIGURE 1. |
| | (3) ANY COMMERCIAL, INDUSTRIAL, OR MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, WHICH |
| | USES HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH AN |
| | APPROVED SYMBOL. TOWNHOUSES ARE NOT MULTIUNIT |
| | RESIDENTIAL STRUCTURES AND THEREFORE NOT SUBJECT TO |
| | THIS RULE. EACH APPROVED SYMBOL SHALL INCLUDE WITHIN |
| | THE CENTER CIRCLE ONE OF THE FOLLOWING DESIGNATIONS: |
| | (A) STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER ?R?. |
| | (B) STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER ?F?. |
| | (C) STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS ?RF.? |
| | (4) THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 |
| | INCHES TO THE LEFT OF THE MAIN ENTRY DOOR AND: |
| | (A) BE PERMANENTLY ATTACHED TO THE FACE OF THE |
| | STRUCTURE ON A CONTRASTING BACKGROUND; OR |
| | (B) BE MOUNTED ON A CONTRASTING BASE MATERIAL WHICH IS |
| | THEN PERMANENTLY ATTACHED TO THE FACE OF THE STRUCTURE. |
| | (5) THE DISTANCE ABOVE THE GRADE, WALKING SURFACE OR |
| | THE FINISHED FLOOR TO THE BOTTOM OF THE SYMBOL SHALL BE |
| | NOT LESS THAN 4 FEET (48 IN.). |
| | (6) THE DISTANCE ABOVE THE GRADE, WALKING SURFACE OR |
| | THE FINISHED FLOOR TO THE TOP OF THE SYMBOL SHALL BE |
| | NOT MORE THAN 6 FEET (72 IN.). |
| | (7) IN SINGLE TENANT STRUCTURES WITH MULTIPLE MAIN |
| | ENTRY DOORS, SUCH AS BIG BOX RETAIL STORES, DEPARTMENT |
| | STORES AND GROCERY STORES, THE AUTHORITY HAVING |
| | JURISDICTION IS AUTHORIZED TO REQUIRE THAT OTHER MAIN |
| | ENTRY DOORS OF THE STRUCTURE BE MARKED WITH AN APPROVED |
| | SYMBOL TO CARRY OUT THE PURPOSE IN SUBSECTION (1) |
| | ABOVE. |
| | (8) IN MULTIPLE TENANT STRUCTURES AND COVERED MALL |
| | STRUCTURES WITH MULTIPLE MAIN ENTRY DOORS, THE |
| | AUTHORITY HAVING JURISDICTION IS AUTHORIZED TO REQUIRE |
| | THAT OTHER MAIN ENTRY DOORS OF THE STRUCTURE BE MARKED |
| | WITH AN APPROVED SYMBOL TO CARRY OUT THE PURPOSE IN |
| | SUBSECTION (1) ABOVE. |
| | (9) IN MULTIPLE TENANT STRUCTURES AND COVERED MALLS |
| | WITH MULTIPLE MAIN ENTRY DOORS, THE AUTHORITY HAVING |
| | JURISDICTION IS AUTHORIZED TO REQUIRE THAT OTHER MAIN |
| | ENTRY DOORS BE MARKED WITH AN APPROVED SYMBOL TO CARRY |
| | OUT THE PURPOSE IN SUBSECTION (1) ABOVE. IN SUCH |
| | STRUCTURES, APPROVED SYMBOLS SHALL BE MARKED ON ONE |
| | SIDE OF THE STRUCTURE ONLY AND SPACED NOT CLOSER THAN |
| | 100 FEET OR AT EACH END OF THE STRUCTURE WHEN SUCH |
| | STRUCTURE IS LESS THAN 100 FEET IN LENGTH. |
| | (10) THE OWNER OF EACH NEW STRUCTURE REQUIRED TO COMPLY |
| | WITH THIS SECTION SHALL MARK THE STRUCTURE WITH THE |
| | APPROVED SYMBOL PRIOR TO RECEIVING A CERTIFICATE OF |
| | OCCUPANCY. |
| | (11) THE OWNER OF EACH EXISTING STRUCTURE REQUIRED TO |
| | COMPLY WITH THIS SECTION SHALL MARK THE STRUCTURE WITH |
| | THE APPROVED SYMBOL WITHIN 90 DAYS OF THE EFFECTIVE |
| | DATE OF THIS RULE. |
| | (12) WHERE THE OWNER OF THE STRUCTURE AND THE AUTHORITY |
| | HAVING JURISDICTION DISAGREE AS TO THE USE OF |
| | LIGHT-FRAME TRUSS-TYPE CONSTRUCTION WITHIN THE |
| | STRUCTURE, THE OWNER SHALL BE GRANTED NOT MORE THAN 45 |
| | DAYS TO PROVIDE WRITTEN VERIFICATION FROM A LICENSED |
| | ENGINEER OR LICENSED ARCHITECT; OTHERWISE, THE OWNER |
| | SHALL COMPLY WITH THE RULE. |
| | |
| | PLEASE PROVIDE THE REQUIRED SIGNAGE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |