| 2017-09-13 13:51:17 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED |
| | |
| | 2. PLEASE PROVIDE A FIXTURE COUNT BREAKDOWN. PER WPB |
| | AMEND TO FBC 107.3.5.1.3 |
| | |
| | NEW COMMENT: |
| | |
| | 1.THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM WATER CLOSET DRAINS. THE VENT |
| | SHALL CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 905. THE CIRCUIT |
| | VENT PIPE SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL |
| | OR WASTE. PER FBC PL 914.2 |
| | |
| | 2. PLEASE PROVIDE SQFT DRAINED BY ROOF DRAINS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 3. PLEASE EXPAND SANITARY RISER IT IS DIFFICULT TO READ |
| | AND WHEN IT IS SCANNED IN FOR OUR RECORDS IT WILL BE |
| | EVEN HARDER TO READ. WPB AMEND TO FBC 107.2.1.4 |
| | |
| | 4. CIVIL SHT. #7 OF 8 SHOWS A GAS MAIN RUNNING UNDER |
| | PROPOSED BUILDING GAS LINES SHALL NOT RUN UNDER |
| | BUILDING WILL NEED TO BE RELOCATED.PER FBC FG 404.14 |
| | |
| | 5. THE CIVIL SHT #7 OF 8 THE CONFIGURATION OF GREASE |
| | INTERCEPTOR DOES NOT MATCH EXISTING INSTALLATION UNDER |
| | PERMIT 16041215. PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 6. PROVIDE DETAILS FOR ACCESSIBILITY IN BATHROOMS, |
| | DRINKING FOUNTAIN AND CLASSROOM SINKS. PER FBC ACC |
| | CHAPTER 6 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |