| Date |
Text |
| 2017-09-06 15:14:03 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17040807 |
| | 9/6/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) 2ND REQUEST FOR AC COOLING AND HEATING CALCULATIONS, |
| | AND ENERGY CALCULATIONS- PLEASE COMPLY. |
| | |
| | 2) SHEETS M2.1.1 & M2.2.1: THE AC LAYOUT PLANS APPEAR |
| | INCOMPLETE. A) INDICATE WHAT TYPE AND SIZE OF LOW |
| | PRESSURE DUCTWORK IS TO BE INSTALLED AT THE OUTLETS OF |
| | THE VAV BOXES. B) LABEL THE DIFFUSER LOCATIONS IN THE |
| | LOW PRESSURE DUCTWORK AND INDICATE THE CFMS AT EACH. |
| | |
| | 3) M2.1.1, M2.2.1, & M2.2.2: PROVIDE DUCT SMOKE |
| | DETECTORS IN THE RETURN AIR SYSTEMS OF THE NEW RTU'S- |
| | SECTION 606.2.1. |
| | |
| | 4) M2.1.1 & M2.2.1: THE CORRIDORS CANNOT BE USED TO |
| | CONVEY RETURN AIR VIA THE TRANSFERS FROM THE CLASSROOMS |
| | AND OTHER ROOMS TO THE RTU'S- SECTION 601.2. |
| | |
| | 5) M2.1.1 & M6.1: AN EXHAUST VENTILATION SYSTEM IS |
| | REQUIRED FOR THE LAB IN COMPLIANCE WITH TABLE 403.3 |
| | FBC-14 MECHANICAL, AND TABLE 6-4 ASHRAE 62.1-2010. THE |
| | EXHAUST RATE IS CALCULATED AT A RATE OF 1.0 CFMS PER |
| | SQ. FT. REVISE THE PLANS AND CALCULATIONS TO SHOW THE |
| | REQUIRED SYSTEM, AND REVISE THE O/A TABLE TO INCLUDE |
| | THE FRESH AIR RATE FOR THE ROOM. PLEASE NOTE THAT |
| | |
| | RECIRCULATION OF AIR FROM THE SPACE IS PROHIBITED PER |
| | FOOTNOTE G. |
| | |
| | 6) THE RTU EQUIPMENT SCHEDULE INDICATES THAT BOTH RTU-2 |
| | & RTU-4 ARE EQUIPPED WITH ERV'S, HOWEVER NO EXHAUST |
| | SYSTEM IS CONNECTING TO RTU-4. PLEASE CLARIFY. |
| | |
| | 7) M6.1: THE VENTILATION RATE FOR THE CLASSROOMS IS |
| | CALCULATED AT 0.12 CFMS PER SQ. FT. PLEASE CORRECT THE |
| | O/A SCHEDULE. |
| | |
| | 8) PROVIDE COMPLETE STRUCTURAL ENGINEERING AND WIND |
| | DESIGN CRITERIA FOR INSTALLATION OF THE RTU'S- SECTION |
| | 301.15. |
| | |
| | 9) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE RTU'S- |
| | SECTION 307. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |