2017-08-25 14:06:392ND REVIEW COMMENTS:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THE
 SUBMITTED PERMIT, FOUNDATION, SHELL OR ENTIRE BUILDING?
  
 COMPLIED; FULL LIFE SAFETY REVIEW, ENTIRE
 BUILDING/SITE.
  
  
 2) SHEET A 0.01 - THERE ARE INCORRECT REFERNCES TO THE
 CURRENT EDITIONS OF THE FIRE CODE INDICATED.
  
 NOT COMPLIED: THE CURRENT EDITION OF THE FLORIDA FIRE
 PREVENTION CODE IS 2014, AS NOTED IN MY COMMENTS
 PREVIOUSLY; 2015 WAS INSERTED AND IS INCORRECT.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
  
 PLEASE CORRECT.
  
  
  
 3) SHEET A 0.02 - THE GYM ASSEMBLY OCCUPANCY
 CALCULATION IS INDICATED 15/PERSON/SQ FT. OR 400. THERE
 IS NO SEATING PLAN INDICATED AND 15 CAN NOT BE USED,
 7/PERSON/SQ FT SHALL BE USED. THIS RENDERS ALL YOUR
 EGRESS CALCULATION INACCURATE.
  
 NOT COMPLIED. THIS AREA IS MORE THAN AN EXERCISE ROOM
  
 PER NFPA 101, CHAPTER 12, ASSEMBLY OCCUPANCIES AND
 CHAPTER 7 MEANS OF EGRESS.
  
 TABLE 7.3.1.2 OCCUPANCT LOAD FACTOR, CONCENTRATED USE,
 WITHOUT FIXED SEATING 7 NET IS TO BE USED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) SHEET A 0.02 - NOTE # 7 INDICATES AN INCORRECT
 REFERENCE TO NFPA 13.
  
 NOT COMPLIED: THE CURRENT EDITION OF NFPA 13, AS NOTED
 IN MY COMMENTS IS 2010; 2016 WAS INSERTED AND IS
 INCORRECT.
  
 PLEASE CORRECT IT TO 2010 AS NOTED ABOVE.
  
  
  
 5) SHEET A 0.02 - NOTE # 9 INDICATES THAT THE GYM
 OCCUPANCY LOAD BE REDUCED AS A REFLECTION OF THE SCHOOL
 OCCUPANCY. THE CODE IS WRITTEN FOR THE POTENTIAL USE OF
 THE SPACE, NOT JUST THE OCCUPANCY OF THE SCHOOL. THERE
 MAY BE SPECIAL EVENTS OR OTHER ACTIVITES THAT MAY
 SUBJECT THE SPACE TO THE HIGHEST POTENTIAL OCCUPANCY
 LOAD.
  
 NOT COMPLIED.
  
 NFPA 101, CHAPTER & MEANS OF EGRESS.
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA
 ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR
 THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE
 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND
 NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING
 DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS
 SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE
 NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE
 USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
  
 PLEASE REVIEW, CORRECT OR REMOVE THE COMMENT.
  
  
  
 6) SHEET A 2.01 - THERE ARE LIGHWIEGHT TRUSS DESIGNED
 FOR THIS PROJECT.
  
 NOT COMPLIED; A LIGHTWEIGHT TRUSS SIGN IS REQUIRED.
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE FOR THE APPLICABLE SIGNAGE.
  
  
  
  
 7) SHEET A 1.00 - NOTE # 1 INDICATES "DEMOLISH EXISTING
 ALUMINUM STAIR AND STRUCTURE".
  
 NOT COMPLIED. NO REVISION SHEET FOUND, NO REVISION
 DRAWINGS FOUND ON ANY SHEET.
  
 THE EXISTING STAIR AND STRUCTURE IS A REQUIRED EXIT OF
 THE EXISTING SCHOOL.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING
 SCHOOL AND INDICATE IN DETAILS HOW THE EXITING OF THE
 EXISTING SCHOOL WILL BE MAINTAINED DURING ALL
 CONSTRUCTION ACTIVITY UNTIL COMPLETION.
  
  
  
  
 8) SHEET 0.02 - IT IS NOT CLEAR THAT ALL EXITS LEAD TO
 A PUBLIC WAY.
  
 NOT COMPLIED. NO REVISION SHEET FOUND, NO REVISION
 DRAWINGS FOUND ON ANY SHEET.
  
  
 PLEASE PROVIDE AN ENTIRE SITE PLAN INDICATING PASSAGE
 TO A PUBLIC WAY OR AREA OF SAFETY.
  
  
  
 9) ALL SHEETS - IT APPEARS THAT MANY OF THE INTERIOR
 FLOOR PLANS WERE NOT INCLUDED, SO AN ACCURATE REVIEW OF
 THE ENTIRE PROPOSED SCHOOL BUILDING COULD NOT BE
 COMPLETED.
  
 COMPLIED
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  