| Date |
Text |
| 2017-08-25 14:06:39 | 2ND REVIEW COMMENTS: |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THE |
| | SUBMITTED PERMIT, FOUNDATION, SHELL OR ENTIRE BUILDING? |
| | |
| | COMPLIED; FULL LIFE SAFETY REVIEW, ENTIRE |
| | BUILDING/SITE. |
| | |
| | |
| | 2) SHEET A 0.01 - THERE ARE INCORRECT REFERNCES TO THE |
| | CURRENT EDITIONS OF THE FIRE CODE INDICATED. |
| | |
| | NOT COMPLIED: THE CURRENT EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE IS 2014, AS NOTED IN MY COMMENTS |
| | PREVIOUSLY; 2015 WAS INSERTED AND IS INCORRECT. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| | NFPA 110, 2013 EDITION. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 0.02 - THE GYM ASSEMBLY OCCUPANCY |
| | CALCULATION IS INDICATED 15/PERSON/SQ FT. OR 400. THERE |
| | IS NO SEATING PLAN INDICATED AND 15 CAN NOT BE USED, |
| | 7/PERSON/SQ FT SHALL BE USED. THIS RENDERS ALL YOUR |
| | EGRESS CALCULATION INACCURATE. |
| | |
| | NOT COMPLIED. THIS AREA IS MORE THAN AN EXERCISE ROOM |
| | |
| | PER NFPA 101, CHAPTER 12, ASSEMBLY OCCUPANCIES AND |
| | CHAPTER 7 MEANS OF EGRESS. |
| | |
| | TABLE 7.3.1.2 OCCUPANCT LOAD FACTOR, CONCENTRATED USE, |
| | WITHOUT FIXED SEATING 7 NET IS TO BE USED. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 4) SHEET A 0.02 - NOTE # 7 INDICATES AN INCORRECT |
| | REFERENCE TO NFPA 13. |
| | |
| | NOT COMPLIED: THE CURRENT EDITION OF NFPA 13, AS NOTED |
| | IN MY COMMENTS IS 2010; 2016 WAS INSERTED AND IS |
| | INCORRECT. |
| | |
| | PLEASE CORRECT IT TO 2010 AS NOTED ABOVE. |
| | |
| | |
| | |
| | 5) SHEET A 0.02 - NOTE # 9 INDICATES THAT THE GYM |
| | OCCUPANCY LOAD BE REDUCED AS A REFLECTION OF THE SCHOOL |
| | OCCUPANCY. THE CODE IS WRITTEN FOR THE POTENTIAL USE OF |
| | THE SPACE, NOT JUST THE OCCUPANCY OF THE SCHOOL. THERE |
| | MAY BE SPECIAL EVENTS OR OTHER ACTIVITES THAT MAY |
| | SUBJECT THE SPACE TO THE HIGHEST POTENTIAL OCCUPANCY |
| | LOAD. |
| | |
| | NOT COMPLIED. |
| | |
| | NFPA 101, CHAPTER & MEANS OF EGRESS. |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA |
| | ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR |
| | THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE |
| | 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND |
| | NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY, |
| | CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA |
| | FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING |
| | DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS |
| | SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE |
| | NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE |
| | USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED. |
| | |
| | |
| | PLEASE REVIEW, CORRECT OR REMOVE THE COMMENT. |
| | |
| | |
| | |
| | 6) SHEET A 2.01 - THERE ARE LIGHWIEGHT TRUSS DESIGNED |
| | FOR THIS PROJECT. |
| | |
| | NOT COMPLIED; A LIGHTWEIGHT TRUSS SIGN IS REQUIRED. |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PLEASE PROVIDE FOR THE APPLICABLE SIGNAGE. |
| | |
| | |
| | |
| | |
| | 7) SHEET A 1.00 - NOTE # 1 INDICATES "DEMOLISH EXISTING |
| | ALUMINUM STAIR AND STRUCTURE". |
| | |
| | NOT COMPLIED. NO REVISION SHEET FOUND, NO REVISION |
| | DRAWINGS FOUND ON ANY SHEET. |
| | |
| | THE EXISTING STAIR AND STRUCTURE IS A REQUIRED EXIT OF |
| | THE EXISTING SCHOOL. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE EXISTING |
| | SCHOOL AND INDICATE IN DETAILS HOW THE EXITING OF THE |
| | EXISTING SCHOOL WILL BE MAINTAINED DURING ALL |
| | CONSTRUCTION ACTIVITY UNTIL COMPLETION. |
| | |
| | |
| | |
| | |
| | 8) SHEET 0.02 - IT IS NOT CLEAR THAT ALL EXITS LEAD TO |
| | A PUBLIC WAY. |
| | |
| | NOT COMPLIED. NO REVISION SHEET FOUND, NO REVISION |
| | DRAWINGS FOUND ON ANY SHEET. |
| | |
| | |
| | PLEASE PROVIDE AN ENTIRE SITE PLAN INDICATING PASSAGE |
| | TO A PUBLIC WAY OR AREA OF SAFETY. |
| | |
| | |
| | |
| | 9) ALL SHEETS - IT APPEARS THAT MANY OF THE INTERIOR |
| | FLOOR PLANS WERE NOT INCLUDED, SO AN ACCURATE REVIEW OF |
| | THE ENTIRE PROPOSED SCHOOL BUILDING COULD NOT BE |
| | COMPLETED. |
| | |
| | COMPLIED |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |