Plan Review Notes
Plan Review Notes For Permit 17040807
Permit Number 17040807
Review Stop E
Sequence Number 2
Notes
Date Text
2017-08-31 10:48:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 2. RISER DIAGRAM SHOWS EXISTING SERVICE BEING RE-FEED
 AND A "PANEL K" BEING ADDED. PROVIDE MORE DETAILS FOR
 THIS EXISTING SERVICE. WHY IS IT RE-FEED? WHY IS A
 PANEL BEING ADDED? WHAT IS THIS PANEL FEEDING? SHOW
 AREA OF WORK FOR PANEL K AND ALL ASSOCIATED
 INSTALLATION, PROVIDE PANEL SCHEDULE. WHAT IS THE LOAD
 CALCULATION FOR THIS SERVICE? WHERE IS THIS SERVICE
 LOCATED? WHAT IS THE DISTANCE FROM NEW CT LOCATION TO
 EXISTING SERVICE? PROVIDE VOLTAGE DROP CALCULATION.
 RISER SHOWS 3 SETS OF 4-400 KCMIL WITH A 2/0 EQUIPMENT
 GROUNDING CONDUCTOR (EGC). WHY DOES THIS CONDUIT HAVE
 AN EGC? IS THERE A MAIN DISCONNECT NOT SHOWN? WHAT IS
 THE ROUTING OF THIS CONDUIT WITH WIRES THAT HAVE NO
 OVERCURRENT PROTECTION? MANY DETAILS ARE NEEDED. FBC
 107.2.1
 3. PROVIDE MORE DETAIL FOR THE GROUNDING ELECTRODE
 SYSTEM. WHERE IS THE EXISTING GE SYSTEM AND HOW WILL
 THIS SYSTEM BE CONNECTED TO IT? SHOW ALL AVAILABLE
 GROUNDING ELECTRODES AND THE METHOD OF CONNECTION. NEC
 250.50; FBC 107.2.1
 4. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, SOLAR, ETC. FBC 105.1
 5. RISER SHOWS THE TESLA POWERWALL CONNECTED TO PANEL
 IT, BUT PANEL MDP SHOWS SOLAR TIE IN. PROVIDE
 CLARIFICATION. NEC 215.5, FBC 107.2.1
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT. NEC
 250.94
 9. PROVIDE NOTE THAT EXIT AND EMERGENCY LIGHTS WILL BE
 CONNECTED TO THE LIGHTING CIRCUIT IN THE AREA AHEAD OF
 ANY CONTROL. NEC 700.12(F)
 10. PROVIDE MANUFACTURERS SPEC SHEETS FOR LIGHT
 FIXTURES TO CONFIRM LISTING. NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  