| 2017-08-31 10:48:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. FBC CE 405.7.1 |
| | 2. RISER DIAGRAM SHOWS EXISTING SERVICE BEING RE-FEED |
| | AND A "PANEL K" BEING ADDED. PROVIDE MORE DETAILS FOR |
| | THIS EXISTING SERVICE. WHY IS IT RE-FEED? WHY IS A |
| | PANEL BEING ADDED? WHAT IS THIS PANEL FEEDING? SHOW |
| | AREA OF WORK FOR PANEL K AND ALL ASSOCIATED |
| | INSTALLATION, PROVIDE PANEL SCHEDULE. WHAT IS THE LOAD |
| | CALCULATION FOR THIS SERVICE? WHERE IS THIS SERVICE |
| | LOCATED? WHAT IS THE DISTANCE FROM NEW CT LOCATION TO |
| | EXISTING SERVICE? PROVIDE VOLTAGE DROP CALCULATION. |
| | RISER SHOWS 3 SETS OF 4-400 KCMIL WITH A 2/0 EQUIPMENT |
| | GROUNDING CONDUCTOR (EGC). WHY DOES THIS CONDUIT HAVE |
| | AN EGC? IS THERE A MAIN DISCONNECT NOT SHOWN? WHAT IS |
| | THE ROUTING OF THIS CONDUIT WITH WIRES THAT HAVE NO |
| | OVERCURRENT PROTECTION? MANY DETAILS ARE NEEDED. FBC |
| | 107.2.1 |
| | 3. PROVIDE MORE DETAIL FOR THE GROUNDING ELECTRODE |
| | SYSTEM. WHERE IS THE EXISTING GE SYSTEM AND HOW WILL |
| | THIS SYSTEM BE CONNECTED TO IT? SHOW ALL AVAILABLE |
| | GROUNDING ELECTRODES AND THE METHOD OF CONNECTION. NEC |
| | 250.50; FBC 107.2.1 |
| | 4. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV, |
| | PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS, |
| | HOODS, SOLAR, ETC. FBC 105.1 |
| | 5. RISER SHOWS THE TESLA POWERWALL CONNECTED TO PANEL |
| | IT, BUT PANEL MDP SHOWS SOLAR TIE IN. PROVIDE |
| | CLARIFICATION. NEC 215.5, FBC 107.2.1 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. PROVIDE INTERSYSTEM BONDING TERMINATION POINT. NEC |
| | 250.94 |
| | 9. PROVIDE NOTE THAT EXIT AND EMERGENCY LIGHTS WILL BE |
| | CONNECTED TO THE LIGHTING CIRCUIT IN THE AREA AHEAD OF |
| | ANY CONTROL. NEC 700.12(F) |
| | 10. PROVIDE MANUFACTURERS SPEC SHEETS FOR LIGHT |
| | FIXTURES TO CONFIRM LISTING. NEC 110.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |