Plan Review Notes
Plan Review Notes For Permit 17040807
Permit Number 17040807
Review Stop B
Sequence Number 2
Notes
Date Text
2017-09-22 08:59:48***CORRECTIONS***
 REVISED 9/26/17 (ITEM #1)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 GREENE SCHOOL CLASSROOM & GYMNASIUM EXPANSION
 REVIEW #2
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. A GEOTECHNICAL REPORT IS REQUIRED, FBC B 1803.1.
 SEOR IS TO REVIEW THE SOILS REPORT; PROVIDE A SHOP
 DRAWING REVIEW, A REVIEW LETTER, OR INCORPORATE
 REFERENCE INTO THE PLAN. THE REPORT SUBMITTED IS FOR A
 PROJECT AT ANOTHER LOCATION; IT IS NOT CLEAR WHY THIS
 WAS SUBMITTED, FBC B 1803.1, FBC 107.
  
 2ND REVIEW, TWO SOILS REPORTS PROVIDED, THREE REQUIRED.
 ADVISE AS TO WHERE STRUCTURAL ENGINEER OF RECORD'S
 REVIEW CAN BE FOUND. IF NOT IN THE PLAN, PROVIDE A
 LETTER OR SHOP DRAWING REVIEW STAMP ON THE SOILS
 REPORT, FBC 107.
  
 **REVISED ON 9/26/17: IF THE FOUNDATION PERMIT 17060234
 HAS BEEN ISSUED PRIOR TO NEXT REVIEW FOR THIS PERMIT,
 THE SOILS REPORT WILL NOT REQUIRED TO BE SUBMITTED AS
 IT WILL BE A PART OF THE PERMIT RECORD. REVIEW BY SEOR
 IS STILL REQUIRED.**
  
 2-5. OK
  
 6. A SITE PLAN PREPARED BY A DESIGN PROFESSIONAL IS
 REQUIRED TO SHOW COMPLIANCE WITH FBC B TABLES 602, 705.
 THE SITE PLAN SUBMITTED IS NOT SIGNED AND SEALED AND
 DOES NOT INCLUDE THIS INFORMATION.
  
 2ND REVIEW, SHEET A1.01 DOES NOT INCLUDE DIMENSIONS TO
 THE (PROPOSED NEW) PROPERTY LINES OR CENTERLINE OF
 STREET AS APPLICABLE. SEE FBC B TABLES 602, 705.
  
 7. FBC 109, PROJECT VALUE NOT CLEAR. A COPY OF THE
 CONTRACT, COST BREAKDOWN, OTHER INFORMATION MAY BE
 REQUIRED. AS SCOPE IS NOT CLEAR, A VALUATION ADJUSTMENT
 MAY BE DONE AT TIME OF 2ND REVIEW.
  
 2ND REVIEW, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB. VALUE APPEARS LOW. A COST BREAKDOWN MAY BE
 REQUIRED.
  
 8. SEE PREVIOUS LIST REGARDING FBC B 503 COMPLIANCE.
 BUILDING APPEARS TO BE COMPLIANT BUT INFORMATION ON THE
 PLAN IS NOT CORRECT. SHEET A0.02 AND OTHER LOCATIONS,
 REVISE THE FOLLOWING (AND CHECK ALL):
  
 TYPE IIB AND TYPE IIIB CONSTRUCTION DECLARED (APPEARS
 TO BE TYPE IIIB, REVIEWED AS SUCH). REVISE; ONLY ONE IS
 APPLICABLE.
 A5 OCCUPANCY DECLARED; THIS IS FOR OUTDOOR SPORTS,
 REVISE, FBC B 303.5, 303.6.
  
 9. OK - UPDATE OCCUPANT LOAD IF ASSEMBLY OCC LOAD IS
 INCREASED
  
 10-11. OK
  
 12. SEATING AND SIGHT LINES FOR ASSEMBLY SEATING NOT
 CLEAR, REVISE PLAN TO CLARIFY FBC A 802. REVISE PLAN TO
 PROVIDE MORE INFORMATION ABOUT HOW THE SPACE WILL BE
 USED. IT APPEARS THAT COMPANION SEATING MAY ALSO BE
 REQUIRED. IF BLEACHER STYLE SEATING IS INCLUDED, WILL
 THE EXCEPTION OF FBC B 1006.2 BE USED? NO ELECTRICAL
 PLAN SUBMITTED; NOT ENOUGH INFORMATION PROVIDED TO
 DETERMINE CODE COMPLIANCE.
  
 2ND REVIEW, NOT CLEAR HOW THIS HAS BEEN ADDRESSED.
  
 13. OK
  
 14. 2ND REVIEW, SHEET A1.01 SHOWS A SAFE DISPERSAL AREA
 FBC B 1027.5 EXCEPTION (TO REQUIREMENT FOR EXIT
 DISCHARGE TO THE PUBLIC WAY). IF OCCUPANT LOAD IS
 INCREASED DUE TO OTHER COMMENTS, REVISE THIS PAGE.
 ALSO, REVISE THE PLAN TO LABEL THE ROW OF RECTANGLES
 (NOT CLEAR WHAT THIS IS).
  
 15. FBC A 207, REVISE PLAN TO DECLARE METHOD OF
 ACCESSIBLE MEANS OF EGRESS SELECTED. REVISE PLAN TO
 SHOW COMPLIANCE; SEE ALSO COMMENT #14.
  
 2ND REVIEW, NOT CLEAR HOW THIS WAS ADDRESSED. IBC2000
 OR IBC2003?
  
 16. THIS PERMIT WILL BE ISSUED WITH PROVISO, COMPLIANCE
 WITH MEANS OF EGRESS ILLUMINATION, INCLUDING EXIT
 DISCHARGE TO THE PUBLIC WAY, IS TO COMPLY WITH FBC B
 1006.1. THIS WILL BE VERIFIED PRIOR TO C.O. REVISE PLAN
 TO NOTE REQUIREMENT.
  
 17-20. OK
  
 21. ENERGY CALCS WERE PROVIDED BUT APPEAR INCOMPLETE.
 INPUT REPORT DOES NOT SHOW WALLS, DOORS, WINDOWS,
 FENESTRATION, ROOF, ETC. FBC EC 103.
  
 NEW COMMENTS:
  
 22. SHEET A0.02, A0.03, POSSIBLY OTHER SHEETS, IT IS
 NOT CLEAR WHAT WORK IS EXISTING, COVERED BY OTHER
 PERMIT(S), OR PROPOSED UNDER THIS PERMIT. VERIFY THAT
 THE NORTH INDICATOR IS CORRECT ON ALL SHEETS. THE FLOOR
 PLAN FOR EXISTING BUILDING HAS NOT BEEN REVIEWED AT
 THIS TIME. IF THIS IS TO BE INCLUDED IN THE SCOPE OF
 THIS PERMIT, REVISE PLAN TO INDICATE WHAT WORK IS
 PROPOSED. IF THIS WAS PROVIDED FOR INFORMATION ONLY,
 PLEASE LABEL AS SUCH.
  
 23. A0.04, SEE FIRE COMMENTS, FBC B 1004, PROVIDE
 RATIONALE FOR 15SF PER PERSON FOR THE GYMNASIUM. NO
 SEATING IS SHOWN. FOR ALL ASSEMBLY AREAS (PROPOSED, AND
 WHAT MAY BE EXISTING) THE PLAN LACKS CLARIFICATION
 REGARDING THE USE OF THE SPACES.
  
 F0R INSTANCE, GYMANSIUM; WILL THIS BE USED FOR ANY
 PURPOSE OTHER THAN A BASKETBALL COURT WHICH IS SHOWN
 GRAPHICALLY?.
  
 A0.02, WHAT IS THE USE OF THE 1,315 SF ASSEMBLY SPACE?
  
 24. A0.05 AND OTHER SHEETS, WHAT IS THE USE OF THE "FAB
 LAB", FBC 107, REVISE PLAN TO INCLUDE DESCRIPTON.
 A0.04, A0.05, POSSIBLY OTHER LOCATIONS, TEACHER
 PLANNING ROOM TEXT NOT LEGIBLE, REVISE.
  
 25. VESTIBULES 109A, 208A, REVISE PLAN TO SHOW 18"
 MANEUVERING CLEARANCE REQUIRED BY FBC A
  
 26. 3-A5.51 INCLUDES A REFERENCE TO "FBC 2015", REVISE
 AND CHECK ALL.
  
 27. FBC ACCESSIBILITY, PROVIDE DETAILS FOR BATHROOMS
 AND FIXTURES.
  
 28. FBC A 212.3, SHEET A 5.51, CLARIFY LOCATION OF
 SINKS DETAILS 2 AND 3.
  
 29. THREE COMPLETE IDENTICAL COLLATED SETS OF PERMIT
 DOCUMENTS AND PLANS REQUIRED, FBC 107. FAILURE TO
 PROVIDE THREE SETS FOR EACH REVIEW CYCLE MAY RESULT IN
 DELAY AT TIME OF ISSUANCE.
  
 30. THE DELEGATED ENGINEERING (BUILDING SHELL) IS
 REQUIRED TO BE SIGNED, SEALED, DATED ORIGINALS, FS471.
 THEY ARE TO BE REVIEWED BY STRUCTURAL ENGINEER OF
 RECORD PRIOR TO SUBMITTAL. THEY MAY BE PROVIDED IN THE
 NEXT SUBMITTAL OR MAY BE A DEFERRED SUBMITTAL
 (SUBMITTED, REVIEWED, AND ISSUED PRIOR TO
 INSTALLATION).
  
 31. FBC B TABLE 1607.1(26), SHEET S002 AND E1 OF 68,
 300# CONCENTRATED REQUIRED FOR ROOF, REVISE.
  
 32. FBC 107, PROVIDE THE COVER SHEET FOR EACH FLORIDA
 STATE PRODUCT APPROVAL. THIS WAS PROVIDED FOR SOME BUT
 NOT ALL OF THE PRODUCT APPROVALS. ALL PRODUCT APPROVALS
 AND RELATED INFORMATION (METHOD OF FASTENING PROPOSED)
 MAY BE A DEFERRED SUBMITTAL.
  
 33. VERIFY THAT PRODUCT APPROVALS HAVE PRINTED
 PROPERLY; SEE NOA 16-0208.08.
  
 34. ROOF DECK PRODUCT APPROVALS, WALL PANEL PRODUCT
 APPROVALS, INDICATE WHICH METHOD OF FASTENING IS
 PROPOSED, FBC B 1609. THIS MAY BE A DEFERRED SUBMITTAL.
  
 34. WHEN RESUBMITTING, PROVIDE THREE IDENTICAL COLLATED
 SETS OF PLANS AND PERMIT DOCUMENTS. THE SUPPORTING
 DOCUMENTS MAY BE IN A BINDER BUT IF SUBMITTED IN THIS
 MANNER SHOULD HAVE THREE BINDERS. REMOVE OLD SHEETS
 FROM THE BOUND SETS, MARK VOID AND RETAIN IN THE
 SUBMITTAL (BUT NOT IN THE PLANS FOR PERMIT ISSUANCE).
 ALL CHANGES SHOULD BE CLOUDED AND MARKED WITH REVISION
 #.
  
 35. FS553.80(2)(B), WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  