| Plan Review Notes For Permit 17040776 |
| Permit Number |
17040776 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-26 16:21:18 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. MANY DOORS DO NOT APPEAR TO HAVE THE 18" MANEUVERING | | | CLEARANCE REQUIRED, PULL SIDE, FBC A 202.4, FIGURE | | | 404.2.4.1. REVISE PLAN; SEE DOORS EXAM 108, EXAM 106, | | | EXAM 105, OFFICE 104, SUPPLY 113, CHECK ALL. IT IS NOT | | | CLEAR WHY SO MANY OF THE EXISTING DOORS DO NOT COMPLY. | | | IF ALL DOORS ARE NOT FIXED, PLEASE CONTACT ME PRIOR TO | | | RESUBMITTAL. | | | | | | 2. ADVISE AS TO STATUS OF EXPIRED ABANDONED PERMIT | | | APPLICATIONS 13060827,15010788,15010790 (AND POSSIBLY | | | OTHERS) TO INSTALL A 80KW DIESEL GENERATOR AND FUEL | | | TANK. THIS PROPERTY ALSO HAS SEVERAL OTHER EXPIRED | | | PERMITS. FOR ASSISTANCE IN RESOLVING THE EXPIRED | | | PERMITS, PLEASE CONTACT: | | | | | | [email protected] | | | 561-805-6690 | | | | | | OF PARTICULAR CONCERN ARE THE ABANDONED GENERATOR AND | | | FUEL TANK APPLICATIONS. | | | | | | 3. FBC A, FBC 107, PROVIDE A COPY OF THE CONTRACT FOR | | | THIS JOB. A COST BREAK DOWN MAY BE REQUIRED. | | | | | | 4. SEE LOUNGE DOORS AND FBC A 404.2.6, SHOW DISTANCE | | | BETWEEN THE TWO DOORS. | | | | | | |
|