2017-04-26 16:21:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. MANY DOORS DO NOT APPEAR TO HAVE THE 18" MANEUVERING
 CLEARANCE REQUIRED, PULL SIDE, FBC A 202.4, FIGURE
 404.2.4.1. REVISE PLAN; SEE DOORS EXAM 108, EXAM 106,
 EXAM 105, OFFICE 104, SUPPLY 113, CHECK ALL. IT IS NOT
 CLEAR WHY SO MANY OF THE EXISTING DOORS DO NOT COMPLY.
 IF ALL DOORS ARE NOT FIXED, PLEASE CONTACT ME PRIOR TO
 RESUBMITTAL.
  
 2. ADVISE AS TO STATUS OF EXPIRED ABANDONED PERMIT
 APPLICATIONS 13060827,15010788,15010790 (AND POSSIBLY
 OTHERS) TO INSTALL A 80KW DIESEL GENERATOR AND FUEL
 TANK. THIS PROPERTY ALSO HAS SEVERAL OTHER EXPIRED
 PERMITS. FOR ASSISTANCE IN RESOLVING THE EXPIRED
 PERMITS, PLEASE CONTACT:
  
 [email protected]
 561-805-6690
  
 OF PARTICULAR CONCERN ARE THE ABANDONED GENERATOR AND
 FUEL TANK APPLICATIONS.
  
 3. FBC A, FBC 107, PROVIDE A COPY OF THE CONTRACT FOR
 THIS JOB. A COST BREAK DOWN MAY BE REQUIRED.
  
 4. SEE LOUNGE DOORS AND FBC A 404.2.6, SHOW DISTANCE
 BETWEEN THE TWO DOORS.
  
  