| 2017-05-09 10:47:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. THERE IS NO EVIDENCE OF A PERMIT FOR THE ENCLOSURE |
| | OF THE PORCH. PLANS FOR THE PORCH (PERMIT 11817J ISSUED |
| | 3/20/87) SHOW A ROOF AND COLUMNS WITH MINIMAL |
| | ELECTRICAL WORK. |
| | |
| | EITHER PROVIDE THE PERMIT NUMBER UNDER WHICH THIS AREA |
| | WAS CONVERTED FROM AN OPEN PORCH TO ENCLOSED HABITABLE |
| | AREA, SUBMIT PLANS FOR THE PORCH CONVERSION, OR OBTAIN |
| | A PERMIT TO DEMOLISH THE WORK INSTALLED WITHOUT PERMIT. |
| | |
| | 2. FBC 107, PLANS ARE TO BE ARCHITECTURAL QUALITY, TO |
| | SCALE, SUFFICIENT TO SHOW WORK PROPOSED. DO NOT LABEL |
| | ELEMENTS INSTALLED WITHOUT A PERMIT AS "EXISTING" AS |
| | "EXISTING" IS A TERM TO DESCRIBE ELEMENTS WHICH WERE |
| | PERMITTED, INSPECTED, OBTAINED FINAL INSPECTION, AND |
| | PERMIT CLOSED. ELEMENTS INSTALLED WITHOUT PERMIT, OR |
| | VIA A PERMIT WITH INCORRECT OR MISLEADING INFORMATION |
| | (SUCH AS THE WINDOW PERMIT WHICH CALLED THE WORK A |
| | "REPLACEMENT"), ARE SUGGESTED TO BE LABELED AS |
| | "PREVIOUSLY INSTALLED" OR OTHER SIMILAR LANGUAGE WITH A |
| | GENERAL NOTE TO CLARIFY THAT THE WORK HAS ALREADY BEEN |
| | DONE. |
| | |
| | A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME DUE TO A |
| | LACK OF INFORMATION. SOME ITEMS TO INCLUDE ON THE PLAN: |
| | |
| | A BASIC FLOOR PLAN OF THE REAR OF THE HOUSE SHOWING |
| | ROOMS, ALL OPENINGS (BOTH OPENINGS STILL IN PLACE AND |
| | OPENINGS WHICH HAVE BEEN CLOSED UP) WITH DIMENSIONS AND |
| | WINDOW/DOOR TYPE |
| | |
| | FOR BEDROOMS ADJACENT TO THE PORCH, SHOW ALL OPENINGS |
| | TO THE OUTSIDE (WINDOWS AND DOORS) INCLUDING DIMENSIONS |
| | |
| | PROVIDE DETAILS FOR THE WALLS, FOUNDATION THROUGH THE |
| | ROOF. SHOW FINISHED FLOOR RELATIVE TO GRADE. |
| | |
| | WAS A CEILING INSTALLED? INSULATION? DRYWALL? |
| | DOORS/WINDOWS BETWEEN HOUSE AND PORCH LEFT IN PLACE, OR |
| | REMOVED? PLAN TO INCLUDE ALL ELEMENTS INSTALLED OR |
| | REMOVED. |
| | |
| | PLAN TO INCLUDE HOUSE EXISTING SQUARE FOOT UNDER AIR, |
| | PROPOSED "NEW" (PREVIOUSLY CONVERTED), NEW TOTAL - SEE |
| | ALSO IMPACT FEE REVIEW. |
| | |
| | 3. SEE IMPACT FEE REVIEW. |
| | |
| | 4. PERMIT VALUATION IS TO INCLUDE THE VALUE OF WORK, |
| | EVEN IF PREVIOUSLY DONE AND BEING PERMITTED AT THIS |
| | TIME, FBC 109. |
| | |