2017-07-24 16:54:242ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040737
 7/24/17
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE SUBMITTED ENERGY FORM C402 IS ACCEPTABLE FOR THE
 RENOVATED POTION OF THE BUILDING BUT CANNOT BE USED FOR
 THE NEW CONDITIONED GARAGE ADDITION WHICH MUST MEET
 FULL COMPLIANCE- SEE SECTION C101.4.3 FBC-14 ENERGY
 CONSERVATION.
  
 2) SHEET M6.3: THE REVISED VENTIALTION CALCULATIONS DO
 NOT INCLUDE AHU'S 6, 7, & 8 WHICH ARE SYSTEMS SUPPLYING
 THE FITNESS CENTER, MEZZANINE, KIDS ROOM, AND THE
 CLUBROOM.
  
 3) AS PREVIOUSLY REQUESTED, PROVIDE THE WIND LOAD
 ENGINEERING FOR TIE DOWN OF THE EXTERIOR CONDENSER
 (CU-G).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER