| 2017-07-24 16:54:24 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040737 | | | 7/24/17 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | 1) THE SUBMITTED ENERGY FORM C402 IS ACCEPTABLE FOR THE | | | RENOVATED POTION OF THE BUILDING BUT CANNOT BE USED FOR | | | THE NEW CONDITIONED GARAGE ADDITION WHICH MUST MEET | | | FULL COMPLIANCE- SEE SECTION C101.4.3 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) SHEET M6.3: THE REVISED VENTIALTION CALCULATIONS DO | | | NOT INCLUDE AHU'S 6, 7, & 8 WHICH ARE SYSTEMS SUPPLYING | | | THE FITNESS CENTER, MEZZANINE, KIDS ROOM, AND THE | | | CLUBROOM. | | | | | | 3) AS PREVIOUSLY REQUESTED, PROVIDE THE WIND LOAD | | | ENGINEERING FOR TIE DOWN OF THE EXTERIOR CONDENSER | | | (CU-G). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|