Plan Review Notes
Plan Review Notes For Permit 17040737
Permit Number 17040737
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-04 14:06:291ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040737
 5/4/17
  
 1) BASED ON THE PROJECT INFORMATION LISTED ON SHEET
 A0.03 COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION
 CODE COMPLIANCE IS REQUIRED. THE PROJECT IS LISTED AS A
 LEVEL III ALTERATION, WITH AREAS THAT ARE DESIGNATED AS
 CHANGES OF OCCUPANCY, AND THERE IS AN NEW CONDITIONED
 GARAGE SHOWN ON THE PLANS. PLEASE REFER TO SECTIONS
 C101.4.3 AND C101.4.4 AND PROVIDE ENERGY
  
 CALCULATIONS. SEE SECTION C101.5 FOR COMPLIANCE
 SUBMITTALS, AND C401.2 FOR COMPLIANCE PATHS.
  
 2) SHEET M-6.1: THE SUBMITTED AC COOLING AND HEATING
 CALCULATIONS ARE INDICATING SYSTEMS 2-8 AS SHOWN ON THE
 SCHEDULE ARE OVERSIZED- SEE SECTION C403..2.2 AND
 CORRECT.
  
 3) PROVIDE AC CALCULATIONS FOR THE DUCTLESS SYSTEM IN
 THE GARAGE- CU-G/AHU-G.
  
 4) M-1.1: THE OUTSIDE AIR CALCULATIONS ARE INCOMPLETE
 AND NOT IN COMPLIANCE WITH TABLE 403.3 FBC-14
 MECHANICAL. PLEASE CORRECT THE SCHEDULE SO THAT IT
 INDICATES THE ROOMS OR SPACES THAT THE O/A IS BEING
 SUPPLIED TO, AND INCLUDES THE CORRECT CFMS PER PERSON
 AND CFMS PER SQ. FT. CALCULATION AS REQUIRED BY TABLE
 403.3. THE CURRENT PLAN IS INDICATING O/A CFMS THAT
 DON'T MATCH
  
 THE CFMS IN THE SCHEDULE.
  
 5) M-6.2: PROVIDE THE WIND LOAD DESIGN CRITERIA AND THE
 LATERAL AND UPLIFT PRESSURES USED IN DETERMINING THE
 CONDENSER ANCHORING DETAILS- SECTION 301.15.
  
 6) M-6.2: REVISE THE AHU DETAILS TO SHOW THE PRIMARY
 AND SECONDARY CONDENSATE PIPING DETAILS- SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  