2017-04-26 17:14:054400 PORTOFINO WAY - CLUBHOUSE
 PERMIT #17040737
 FIRE DEPARTMENT COMMENTS:
  
 GENERAL:
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT WHEN THE SCOPE
 OF WORK AFFECTS 50 OR MORE SPRINKLERS. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
  
 SHEET A0.07:
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SEVERAL EXITS APEAR TO BE ROUTED THROUGH THE POOL DECK
 AREA. THIS WILL REQUIRE THE LIFE SAFETY PLAN TO INCLUDE
 THE OCCUPANTS EGRESSING FROM THE POOL AREA AND SHOWING
 THE EXITS DISCHARGING TO A PUBLIC WAY.
  
 IF THE POOL DECK IS BEING USED TO EGRESS BUILDING
 OCCUPANTS, HOW ARE CHILDREN BEING PROTECTED FROM
 UNRESTRICTED ACCESS INTO THE POOL?
  
 PROVIDE A FURNITURE/EQUIPMENT/SEATING PLAN FOR THE
 FITNESS, KID FITNESS AND CLUB ROOM JUSTIFYING THE USE
 OF 50 AND 15 SQ.FT. OCCUPANT LOAD FACTORS.
  
 THE CONFERENCE ROOM SHOULD BE CALCULATED USING AN
 OCCUPANT LOAD FACTOR OF 15 SQ.FT. IN LIEU OF 100 SQ.FT.
  
 THE LARGE OPEN LOBBY ADJACENT TO THE COFFEE BAR IS
 PRIME SPACE FOR OCCUPANTS TO UTILIZE AS AN ASSEMBLY
 SPACE. THE OFFICE DOES NOT SUPPORT THE DESIGNATION OF
 THIS SPACE AS A BUSINESS OCCUPANCY WITH ONLY 12
 OCCUPANTS.
  
 DESCRIBE WHAT WILL BE STORED IN THE GARAGE. WILL ANY
 GENERAL MAINTENANCE ACTIVITIES OCCUR IN THIS SPACE?
  
  
 SHEET A0.08:
 THE EXERCISE MEZZANINE INDICATES AN OCCUPANT LOAD
 FACTOR OF 50 SQ.FT.; HOWEVER, MORE THAN HALF OF THE
 FLOOR SPACE DOES NOT INDICATE ANY EQUIPMENT JUSTIFYING
 THE LOAD FACTOR.