| 2017-04-26 17:14:05 | 4400 PORTOFINO WAY - CLUBHOUSE |
| | PERMIT #17040737 |
| | FIRE DEPARTMENT COMMENTS: |
| | |
| | GENERAL: |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT WHEN THE SCOPE |
| | OF WORK AFFECTS 50 OR MORE SPRINKLERS. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | |
| | SHEET A0.07: |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | SEVERAL EXITS APEAR TO BE ROUTED THROUGH THE POOL DECK |
| | AREA. THIS WILL REQUIRE THE LIFE SAFETY PLAN TO INCLUDE |
| | THE OCCUPANTS EGRESSING FROM THE POOL AREA AND SHOWING |
| | THE EXITS DISCHARGING TO A PUBLIC WAY. |
| | |
| | IF THE POOL DECK IS BEING USED TO EGRESS BUILDING |
| | OCCUPANTS, HOW ARE CHILDREN BEING PROTECTED FROM |
| | UNRESTRICTED ACCESS INTO THE POOL? |
| | |
| | PROVIDE A FURNITURE/EQUIPMENT/SEATING PLAN FOR THE |
| | FITNESS, KID FITNESS AND CLUB ROOM JUSTIFYING THE USE |
| | OF 50 AND 15 SQ.FT. OCCUPANT LOAD FACTORS. |
| | |
| | THE CONFERENCE ROOM SHOULD BE CALCULATED USING AN |
| | OCCUPANT LOAD FACTOR OF 15 SQ.FT. IN LIEU OF 100 SQ.FT. |
| | |
| | THE LARGE OPEN LOBBY ADJACENT TO THE COFFEE BAR IS |
| | PRIME SPACE FOR OCCUPANTS TO UTILIZE AS AN ASSEMBLY |
| | SPACE. THE OFFICE DOES NOT SUPPORT THE DESIGNATION OF |
| | THIS SPACE AS A BUSINESS OCCUPANCY WITH ONLY 12 |
| | OCCUPANTS. |
| | |
| | DESCRIBE WHAT WILL BE STORED IN THE GARAGE. WILL ANY |
| | GENERAL MAINTENANCE ACTIVITIES OCCUR IN THIS SPACE? |
| | |
| | |
| | SHEET A0.08: |
| | THE EXERCISE MEZZANINE INDICATES AN OCCUPANT LOAD |
| | FACTOR OF 50 SQ.FT.; HOWEVER, MORE THAN HALF OF THE |
| | FLOOR SPACE DOES NOT INDICATE ANY EQUIPMENT JUSTIFYING |
| | THE LOAD FACTOR. |