| 2017-05-24 11:54:48 | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION |
| | |
| | PROVIDE CUT SHEETS FOR FIXTURES. |
| | |
| | PAGE E1.1L |
| | |
| | C405.5 INTERIOR LIGHTING POWER REQUIREMENTS |
| | (PRESCRIPTIVE). |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. |
| | |
| | C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER. |
| | THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS) |
| | SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR LIGHTING |
| | EQUIPMENT AS DETERMINED |
| | IN ACCORDANCE WITH SECTIONS C405.5.1.1 THROUGH |
| | C405.5.1.4. |
| | |
| | |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND |
| | C405.2.4. |
| | |
| | C405.2.1 MANUAL LIGHTING CONTROLS. |
| | ALL BUILDINGS SHALL INCLUDE MANUAL LIGHTING CONTROLS |
| | THAT MEET THE REQUIREMENTS OF SECTIONS C405.2.1.1 AND |
| | C405.2.1.2. |
| | |
| | C405.2.1.1 INTERIOR LIGHTING CONTROLS. |
| | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING |
| | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL FOR |
| | THE LIGHTING SERVING THAT AREA. |
| | THE REQUIRED CONTROLS SHALL BE LOCATED WITHIN THE AREA |
| | SERVED BY THE CONTROLS OR BE A REMOTE SWITCH THAT |
| | IDENTIFIES THE LIGHTS SERVED |
| | AND INDICATES THEIR STATUS. |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE |
| | OFFICES, RESTROOMS, STORAGE ROOMS AND JANITORIAL |
| | CLOSETS, AND OTHER SPACES 300 SQUARE FEET (28 M2) OR |
| | LESS ENCLOSED BY FLOOR-TO- |
| | CEILING HEIGHT PARTITIONS. THESE AUTOMATIC CONTROL |
| | DEVICES SHALL BE INSTALLED TO AUTOMATICALLY TURN OFF |
| | LIGHTS WITHIN 30 MINUTES OF |
| | ALL OCCUPANTS LEAVING THE SPACE, AND SHALL EITHER BE |
| | MANUAL ON OR SHALL BE CONTROLLED TO AUTOMATICALLY TURN |
| | THE LIGHTING ON TO NOT |
| | MORE THAN 50 PERCENT POWER. |
| | |
| | PAGE E6.1 |
| | |
| | PANEL SCHEDULES TO VAGUE NEED TO BE MORE SPECIFIC TO |
| | LOCATIONS. |
| | |
| | |