| 2017-05-22 15:07:35 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040737 |
| | ADD: 4400 PORTOFINO WAY |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ?????????? |
| | E-MAIL: [email protected] / SANDY MAKSYM |
| | |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MAY 19/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 003-A0.03 ALLOWABLE BUILDING INCREASES. UNDER |
| | THIS HEADING AREA INCREASES WERE TAKEN FOR FIRE |
| | SPRINKLERS. THE BUILDING MAYBE FIRE SPRINKLERED BUT NO |
| | FIRE SPRINKLER PLANS WERE SUBMITTED UNDER THIS REVIEW. |
| | FIRE SPRINKLER PLANS WILL BE REQUIRED FOR THE |
| | RECONFIGURATION OF SPACE AND FOR BENEATH THE NEW |
| | MEZZANINE LEVEL AS WELL, ADDITIONAL FIRE AREAS WERE |
| | ADDED. |
| | 105.3.1.2 NO PERMIT MAY BE ISSUED FOR ANY BUILDING |
| | CONSTRUCTION, ERECTION, ALTERATION, MODIFICATION, |
| | REPAIR, OR ADDITION UNLESS THE APPLICANT FOR SUCH |
| | PERMIT PROVIDES TO THE ENFORCING AGENCY WHICH ISSUES |
| | THE PERMIT ANY OF THE FOLLOWING DOCUMENTS WHICH APPLY |
| | TO THE CONSTRUCTION FOR WHICH THE PERMIT IS TO BE |
| | ISSUED AND WHICH SHALL BE PREPARED BY OR UNDER THE |
| | DIRECTION OF AN ENGINEER REGISTERED UNDER CHAPTER 471, |
| | FLORIDA STATUTES: 2. FIRE SPRINKLER DOCUMENTS FOR ANY |
| | NEW BUILDING OR ADDITION WHICH INCLUDES A FIRE |
| | SPRINKLER SYSTEM WHICH CONTAINS 50 OR MORE SPRINKLER |
| | HEADS. A CONTRACTOR I, CONTRACTOR II OR CONTRACTOR IV, |
| | CERTIFIED UNDER SECTION 633.521, FLORIDA STATUTES, MAY |
| | DESIGN A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND |
| | MAY DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER |
| | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, |
| | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, |
| | NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 2) SHEET A0.03 UNDER THE APPLICABLE CODES LIST THE FAIR |
| | HOUSING ACT DESIGN MANUAL, AND THE AMERICANS WITH |
| | DISABILITIES ACT, 2010 EDITION ANSI A117.1 2003 EDITION |
| | FOR CODES THAT DEAL WITH ACCESSIBILITY ELEMENTS. THE |
| | 2014 FBC-ACCESSIBILITY CODE IS NOT MENTIONED AS PART OF |
| | THE APPLICABLE CODES. SHEETS A0.05 AND A0.06 INCLUDE |
| | THE 2014 ACCESSIBILITY CODE FOR PUBLIC SPACES |
| | (LEASING). THE WHERE THE MORE STRINGENT OF THE 2 CODES |
| | WILL APPLY FOR THE COMMON USE ELEMENTS, PARKING SPACES |
| | AT THE CLUBHOUSE. A STATEMENT MUST BE ADDED FOR PUBLIC |
| | AND COMMON USE AREAS, WITH THE EXCEPTION OF THE LEASING |
| | OFFICE, THAT THE REMAINDER OF THE CLUBHOUSE IS FOR THE |
| | USE OF THE RESIDENCE AND THEIR GUEST ONLY, NO UNITS ARE |
| | TO BE RENTED OUT AS TIME SHARE UNITS. IF THE COMMON |
| | AREAS ARE MADE AVAILABLE TO THE PUBLIC ONLY |
| | PERIODICALLY, SUCH AS A FESTIVAL OR SEASONAL EVENT, |
| | THEY MUST COMPLY WITH THE 2014 FLORIDA ACCESSIBILITY |
| | CODE WHICH IS MORE RESTRICTIVE THAN THE ADA. |
| | |
| | |
| | 3A) PLEASE NOTE SHEET A0.07 1ST FLOOR LIFE SAFETY PLAN. |
| | OF THE EXERCISE ROOM OF 2931 /50 SQ. FT. WITH AN |
| | OCCUPANT LOAD OF 59. IF EQUIPMENT IS SHOWN, THE AREA |
| | WHERE THE EQUIPMENT IS LOCATED CAN BE TAKEN AT 50 SQ. |
| | FT. / OCCUPANT. IF A PORTION OF THE GYM IS FOR LINE |
| | DANCING, PALATES OR SIMILAR EXERCISING IT CAN BE TAKEN |
| | AT 15 OR THE MORE RESTRICTIVE 7 SQ. FT. 2931/7= 418 |
| | OCCUPANTS. PLEASE SHOW THE AREAS WHERE EQUIPMENT WILL |
| | BE PLACED FOR THE REDUCED OCCUPANT LOAD. ASSEMBLY |
| | OCCUPANT LOADS ARE TAKEN AS NET. |
| | |
| | 3B) PLEASE NOTE SHEET A0.07 1ST FLOOR LIFE SAFETY PLAN. |
| | OF THE EXERCISE ROOM WITH 292 SQ. FT. . IF EQUIPMENT IS |
| | SHOWN, THE AREA WHERE THE EQUIPMENT IS LOCATED CAN BE |
| | TAKEN AT 50 SQ. FT. / OCCUPANT. PLEASE SHOW THE AREAS |
| | WHERE EQUIPMENT WILL BE PLACED FOR THE REDUCED OCCUPANT |
| | LOAD. ASSEMBLY OCCUPANT LOADS ARE TAKEN AS NET. |
| | 4) PLEASE NOTE SHEET A0.08 THE MEZZANINE LIFE SAFETY |
| | PLAN SHOW AN AREA OF 968 SQ. FT. /50 SQ. FT. WITH AN |
| | OCCUPANT LOAD OF20. WHERE THE EQUIPMENT IS SHOWN, 313 |
| | SQ. FT. THIS CAN BE TAKEN AT 50 SQ. FT. / OCCUPANT OR 7 |
| | OCCUPANTS. . IF A PORTION OF THE GYM IS FOR LINE |
| | DANCING, PALATES OR SIMILAR EXERCISING IT CAN BE TAKEN |
| | AT 15 OR THE MORE RESTRICTIVE 7 SQ. FT. 655/7= 94 |
| | OCCUPANTS. PLEASE SHOW THE AREAS WHERE EQUIPMENT WILL |
| | BE PLACED FOR THE REDUCED OCCUPANT LOAD. ASSEMBLY |
| | OCCUPANT LOADS ARE TAKEN AS NET. |
| | |
| | 5) SHEETS A1.2.2 AND A1.2.3 THE EXERCISE ROOM SHOW |
| | DOORS; |
| | 20-100 GROUP HARDWARE 01 |
| | 20-101 GROUP HARDWARE 03 |
| | 20-102 GROUP HARDWARE 03 |
| | I COULD NOT FIND THE HARDWARE SCHEDULE AND COMPLIANCE |
| | WITH 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | WHEN THE OCCUPANT LOAD IS 50 OR MORE PANIC HARDWARE IS |
| | REQUIRED. |
| | |
| | 6) 162_ SHEET SDT-1 DETAIL: |
| | 6A) 4 & 5 BOTH SHOW WEDGE ANCHORS 3-5/8 EMBED. THE |
| | PLANS ARE SILENT IF THE CELLS ARE ALREADY FILED CELLS |
| | OR IF THEY ARE TO BE FILED AND WITH WHAT STRENGTH |
| | GROUT? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6B) DETAIL #4 SHOWS 1 ? X 1 ? X 1/8 INCH CROSS BRACING |
| | BUT NO WELDING TYPE OR LENGTH IS GIVEN? 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 8) SHEET 163_STD-4 DETAILS 1 & 2 SHOW THE USE OF 6X6 |
| | WOOD COLUMNS, SPECIES NOT PROVIDED, AND IN DETAIL 1 THE |
| | USE OF 2 LVLS TO SET ATOP OF THE (2) 6X6 POST. THE |
| | PLANS INDICATE THE USE OF SIMPSON HD3B CONNECTORS AT |
| | THE BASE, NO ATTACHMENT TO THE CONCRETE BLOCK? AND |
| | SIMPSON BEAM HANGERS (LEFT BLANK)? |
| | WILL HANGERS BE REQUIRED OR STRAPS FROM THE WOOD |
| | COLUMNS? |
| | |
| | 9) SHEET A0.07 THE LIFE SAFETY PLAN PLEASE PROVIDE THE |
| | EXITING FROM THE BUILDING , ASSEMBLY AND BUSINESS AREAS |
| | THAT EXIT THROUGH THE POOL DECK. HOW WILL KIDS BE KEPT |
| | FROM THE POOL DECK AND POOL? PLEASE SHOW COMPLIANCE |
| | WITH EFFECTIVE BARRIER.? A BARRIER WHICH CONSISTS OF A |
| | BUILDING, OR EQUIVALENT STRUCTURE, PLUS A 48-INCH (1219 |
| | MM) MINIMUM HEIGHT FENCE ON THE REMAINING SIDES OR A |
| | CONTINUOUS 48-INCH (1219 MM) MINIMUM HEIGHT FENCE. ALL |
| | ACCESS THROUGH THE BARRIER MUST HAVE ONE OR MORE OF THE |
| | FOLLOWING SAFETY FEATURES: ALARM, KEY LOCK OR |
| | SELF-LOCKING DOORS AND GATES. SAFETY COVERS THAT COMPLY |
| | WITH THE AMERICAN SOCIETY FOR TEST MATERIALS STANDARD |
| | F1346-91 (2003) MAY ALSO BE CONSIDERED AS AN EFFECTIVE |
| | BARRIER. |
| | PLEASE SHOW COMPLIANCE WITH FBC-B 454. 1.3.1.9. |
| | |
| | 10) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 12) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |