Plan Review Notes
Plan Review Notes For Permit 17040710
Permit Number 17040710
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-06-23 15:31:591601 FORUM PLACE #700
 PERMIT #17040710
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. PER FBC SECTION 907.1.1
 CONSTRUCTION DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR
 FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION
 CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL."
 PER SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT: DOOR LOCKING ARRANGEMENTS OF THE
 CORRIDORS AND ELEVATOR LOBBY ONLY PROVIDE A SINGLE
 MEANS OF FREE EGRESS FROM THE MEN'S RESTROOM. A SINGLE
 MEANS OF EGRESS IS NOT PERMITTED IN A HIGH-RISE
 BUILDING.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  