2017-04-21 11:54:261ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CODES
 PERMIT #17040710
 4/21/17
  
 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) INDICATE HOW EF-1 WAS SIZED- PROVIDE A CALCULATION.
  
 3) M2.1: PROVIDE FLEX DUCT SIZES ON THE PLAN OR
 RELOCATE THE SCHEDULE FROM SHEET M6.1.
  
 4) M2.1 PROVIDE FIRE OR FIRE/SMOKE DAMPERS FOR THE O/A
 DUCTS AND EXHAUST DUCT PENETRATING THE FIRE-RATED
 ELEVATOR LOBBY WALLS.
  