| 2017-04-21 11:54:26 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CODES | | | PERMIT #17040710 | | | 4/21/17 | | | | | | 1) REFER TO SECTION 809.1 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) INDICATE HOW EF-1 WAS SIZED- PROVIDE A CALCULATION. | | | | | | 3) M2.1: PROVIDE FLEX DUCT SIZES ON THE PLAN OR | | | RELOCATE THE SCHEDULE FROM SHEET M6.1. | | | | | | 4) M2.1 PROVIDE FIRE OR FIRE/SMOKE DAMPERS FOR THE O/A | | | DUCTS AND EXHAUST DUCT PENETRATING THE FIRE-RATED | | | ELEVATOR LOBBY WALLS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|