| 2017-04-19 15:37:11 | 1601 FORUM PLACE #700 |
| | PERMIT #17040710 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION |
| | DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM |
| | SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL." PER SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE |
| | SPRINKLERS. FLORIDA ADMINISTRATIVE CODE SECTION |
| | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| | SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | DOOR LOCKING ARRANGEMENTS OF THE CORRIDORS AND ELEVATOR |
| | LOBBY ONLY PROVIDE A SINGLE MEANS OF FREE EGRESS FROM |
| | THE MEN'S RESTROOM. A SINGLE MEANS OF EGRESS IS NOT |
| | PERMITTED IN A HIGH-RISE BUILDING. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |