| 2017-05-19 08:52:16 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17040694 |
| | 5/19/17 |
| | |
| | RESULTS: DENIED. |
| | |
| | 1) IN HIS REPONSE TO COMMENTS FROM THE 1ST REVIEW, THE |
| | CONTRACTOR IS REQUESTING AN EXCEPTION TO MEETING THE |
| | REQUIREMENTS OF TABLE 403.3 FOR OCCUPANT DENSITY IN THE |
| | WORSHIP AUDITORIUM BASED ON HISTORICAL DATA. PLEASE |
| | MAKE THE REQUEST IN LETTER FORM, AND PROVIDE THE |
| | HISTORICAL DATA. |
| | |
| | 2) REVIEW OF THE AC CALCULATIONS FOR THE TWO SYSTEMS |
| | AC- 1 & 2 SUPPLYING THE AUDITORIUM INDICATE THAT THE |
| | SENSIBLE AND LATENT HEAT GAIN IN BTUH'S FOR OCCUPANTS |
| | IS LESS THAN WHAT IS REQUIRED BY TABLE 6B ACCA MANUAL |
| | N. FOR EXAMPLE THE HEAT GAIN FOR A PERSON SEATED IN A |
| | PLACE OF WORSHIP- MAN, WOMAN, OR CHILD- IS AN AVERAGE |
| | OF 383 BTUH PER THE TABLE BUT THE CALCULATIONS ARE |
| | |
| | INDICATING 278 BTUH PER PERSON. THE RESULT INDICATES |
| | THE SYSTEMS MAY BE UNDERSIZED FOR COOLING. |
| | |
| | 3) AS PREVIOUSLY NOTED IN THE 1ST REVIEW AN ERV IS |
| | REQUIRED FOR DOA-4 PER TABLE AND SECTION C403.2.6 |
| | FBC-14 ENERGY CONSERVATION. PLEASE NOTE THE PLAN |
| | INDICATES 832 CFMS OF AIR BEING EXHAUSTED BY EF-1. |
| | |
| | 4) PLEASE NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR |
| | DUCTS PENETRATING CORRIDOR WALLS IF IT DETERMINED THAT |
| | THE CORRIDOR WALLS WILL HAVE TO CHANGE FROM NON-RATED |
| | TO FIRE-RATED- PLEASE SEE BUILDING PLAN REVIEW |
| | COMMENTS. |
| | |
| | 5) M-501: 2ND REQUEST TO PROVIDE THE WIND LOAD DESIGN |
| | CRITERIA USED TO ESTABLISH THE PRESSURES AND ANCHORING |
| | METHODS FOR THE AC CONDENSERS AND DOA UNIT- SECTION |
| | 1609 FBC-14 BUILDING. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |