Plan Review Notes
Plan Review Notes For Permit 17040694
Permit Number 17040694
Review Stop M
Sequence Number 2
Notes
Date Text
2017-05-19 08:52:162ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040694
 5/19/17
  
 RESULTS: DENIED.
  
 1) IN HIS REPONSE TO COMMENTS FROM THE 1ST REVIEW, THE
 CONTRACTOR IS REQUESTING AN EXCEPTION TO MEETING THE
 REQUIREMENTS OF TABLE 403.3 FOR OCCUPANT DENSITY IN THE
 WORSHIP AUDITORIUM BASED ON HISTORICAL DATA. PLEASE
 MAKE THE REQUEST IN LETTER FORM, AND PROVIDE THE
 HISTORICAL DATA.
  
 2) REVIEW OF THE AC CALCULATIONS FOR THE TWO SYSTEMS
 AC- 1 & 2 SUPPLYING THE AUDITORIUM INDICATE THAT THE
 SENSIBLE AND LATENT HEAT GAIN IN BTUH'S FOR OCCUPANTS
 IS LESS THAN WHAT IS REQUIRED BY TABLE 6B ACCA MANUAL
 N. FOR EXAMPLE THE HEAT GAIN FOR A PERSON SEATED IN A
 PLACE OF WORSHIP- MAN, WOMAN, OR CHILD- IS AN AVERAGE
 OF 383 BTUH PER THE TABLE BUT THE CALCULATIONS ARE
  
 INDICATING 278 BTUH PER PERSON. THE RESULT INDICATES
 THE SYSTEMS MAY BE UNDERSIZED FOR COOLING.
  
 3) AS PREVIOUSLY NOTED IN THE 1ST REVIEW AN ERV IS
 REQUIRED FOR DOA-4 PER TABLE AND SECTION C403.2.6
 FBC-14 ENERGY CONSERVATION. PLEASE NOTE THE PLAN
 INDICATES 832 CFMS OF AIR BEING EXHAUSTED BY EF-1.
  
 4) PLEASE NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR
 DUCTS PENETRATING CORRIDOR WALLS IF IT DETERMINED THAT
 THE CORRIDOR WALLS WILL HAVE TO CHANGE FROM NON-RATED
 TO FIRE-RATED- PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 5) M-501: 2ND REQUEST TO PROVIDE THE WIND LOAD DESIGN
 CRITERIA USED TO ESTABLISH THE PRESSURES AND ANCHORING
 METHODS FOR THE AC CONDENSERS AND DOA UNIT- SECTION
 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  