| 2017-05-19 16:13:06 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040694 |
| | ADD: 3000 N. AUSTRALIAN AVE. |
| | CONT: DOSDOURIAN ENTERPRISES |
| | TEL: 561-844-2990 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MAY 19, 2017 |
| | ACTION: DENIED |
| | |
| | 1A) THE 2014 FBC-EXISTING BUILDING CODE LEVEL II |
| | COMPLIANCE. 805.2 THE MEANS OF EGRESS SHALL COMPLY WITH |
| | THE REQUIREMENTS OF THIS SECTION. |
| | EXCEPTIONS: |
| | 1. WHERE THE WORK AREA AND THE MEANS OF EGRESS SERVING |
| | IT COMPLIES WITH NFPA 101. |
| | 2. MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF |
| | THE BUILDING CODE UNDER WHICH THE BUILDING WAS |
| | CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF |
| | EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO |
| | NOT CONSTITUTE A DISTINCT HAZARD TO LIFE. |
| | |
| | THIS BUILDING WAS BUILT IN 1994 UNDER THE 1991 SSBC. |
| | WHEN REVIEWING IF THE CORRIDORS WERE RATED TABLE 700 |
| | UNDER THE HEADING EXIT ACCESS CORRIDORS WALLS AND |
| | PARTITIONS (1HR.), OPENING PROTECTIVES (20 MIN.). |
| | FOOTNOTE 4 & 5. FOOTNOTE # 5 DEALS WITH GROUP I |
| | BUILDINGS SPRINKLERED. FOOTNOTE 4 SEE SECTION 702.4.2. |
| | EXIT ACCESS CORRIDORS ARE NOT REQUIRED TO BE RATED ON |
| | ANY SINGLE TENANT SPACE IN A GROUP B BUILDING WHEN THE |
| | BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM AND SMOKE DETECTORS |
| | INSTALLED IN RETURN AIR ARRANGED TO SHUT DOWN |
| | MECHANICAL VENTILATION SYSTEMS IN ACCORDANCE WITH THE |
| | STANDARD MECHANICAL CODE. |
| | |
| | I'VE TAKEN THIS CONCERN TO THE BUILDING OFFICIAL SINCE |
| | THIS BUILDING IS NOT SPRINKLERED AND THE CORRIDOR WALL |
| | SHOULD HAVE BEEN RATED FROM THE 1991 SBC. WE HAVE |
| | REVIEWED THE ORIGINAL 12 SHEETS OF PLANS WHEN THE |
| | BUILDING WAS BUILT. |
| | WE HAVE SOME QUESTIONS THE BUILDING OFFICIAL WOULD LIKE |
| | TO HAVE ANSWERED TO MAKE A FINAL DETERMINATION IF HE |
| | WILL REQUIRE FIRE RARING OF CORRIDORS WITH OPENING |
| | PROTECTIVES. THE (2) MECHANICAL CLOSETS SHOWN ON THE |
| | PLANS, ARE THE WALLS FIRE RATED WITH OPENING |
| | PROTECTIVES? PLEASE PROVIDE THE CEILING HEIGHT OF THE |
| | LOBBY, CORRIDORS AND OF THE MAIN AUDITORIUM. PLEASE |
| | ALSO PROVIDE THE HEADER HEIGHTS FOR THE OPENINGS |
| | LEADING INTO THE AUDITORIUM FROM THE CORRIDORS AND |
| | IDENTIFY WHAT APPEARS TO BE A 7.5 FOOT WIDE EITHER |
| | OPENING, SCREEN AND OR WINDOW ON BOTH SIDES OF THE |
| | AUDITORIUM SEPARATING THE AUDITORIUM AND CORRIDOR. FROM |
| | THE LIMITED PLANS THAT WERE ON FILE, IT APPEARS THE |
| | CORRIDOR CEILING IS AT 10 FT. ELEVATION, THE OPENINGS |
| | INTO THE AUDITORIUM ARE ASSUMED ALSO 10 FEET TALL, THE |
| | OPENINGS 7.5 FEET WIDE, HEIGHT UNKNOWN AND THE |
| | AUDITORIUM CEILING IS ASSUMED TO BE 12 FEET ABOVE THE |
| | FINISH FLOOR ELEVATION. IN THEORY WE ARE CONSIDERING |
| | THE LOBBY AS OPEN AND WILL DISPERSE SMOKE INTO THE |
| | CORRIDORS. THE ISSUE IS THERE ENOUGH OPENINGS FROM THE |
| | NON-RATED CORRIDOR INTO THE AUDITORIUM TO ALLOW THE |
| | SMOKE TO ESCAPE TO THE AUDITORIUM CEILING BUILDING DOWN |
| | ALLOWING ENOUGH TIME FOR THE OCCUPANTS TO LEAVE EITHER |
| | THROUGH THE FRONT LOBBY ENTRY OR DIRECTLY USING THE 2 |
| | SIDE EXITS. THE 2 SIDE EXITS THAT LEAD FROM THE |
| | AUDITORIUM ARE SEPARATED BY ? THE MAJOR DIAGONAL |
| | DISTANCE APART CODE COMPLIANT FOR THAT ROOM. |
| | PLEASE PROVIDE A SIGNED AND SEALED ANALYSIS OF THE |
| | BUILDING, PROVIDING WHAT WOULD BE CONSIDERED ALTERNATE |
| | MATERIALS AND METHODS TO BE REVIEWED BY THE BUILDING |
| | OFFICIAL AS EQUAL TO THE CODE AT TIME THE BUILDING WAS |
| | BUILT. |
| | |
| | 1ST ROUND OF COMMENTS. SHEET G003 THE LIFE SAFETY PLAN |
| | INDICATES THIS IS AN A3 OCCUPANCY, BUILDING TYPE III-B/ |
| | NON-SPRINKLERED, BUILDING, WITH AN OCCUPANT LOAD OF |
| | 278. THE PLANS FAILS TO SHOW FIRE RATED CORRIDORS 101, |
| | 105 & 116 ( 2014 FBC-B TABLE 1018.1)WITH OPENING |
| | PROTECTIVES (DOOR & WINDOWS) IN ACCORDANCE WITH TABLE |
| | 716.5. |
| | |
| | 1B) THE MECHANICAL DUCTS THAT PENETRATE THE CORRIDOR |
| | WALLS LISTED ABOVE IN COMMENT 1A WILL NEED TO SHOW |
| | COMPLIANCE WITH FBC-B DUCTS AND AIR TRANSFER OPENINGS , |
| | PENETRATIONS THROUGH FIRE RATED WALLS. |
| | |
| | 1C) COMPLIED. |
| | |
| | 1D) COMPLIED |
| | |
| | 1E) SHEET G003 THE BOTTOM LEFT CORNER OF THE SHEET |
| | INDICATES IN A NOTE ROOMS 111 & 112 TO BE FIRE RATED, |
| | NOT LOCATED IN THE FLOOR PLAN? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED? |
| | |
| | 2) SHEET A103 THE ROOF PLAN, SHEET KEY NOTES: |
| | |
| | 2A)BUILDING PROVISO: A197 REPAIR ROTTING TRUSSES. A |
| | STRUCTURAL ENGINEER WHO WILL PROVIDE DETAILS ON HOW THE |
| | ROTTING TRUSSES ARE GOING TO BE REPAIRED. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2B-D) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |