| 2017-04-18 15:16:59 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. INDICATED THE VOLTAGE FOR THE ELECTRICAL |
| | SERVICE. BOTH 240 VOLT AND 208 VOLTS ARE INDICATED ON |
| | THE DOCUMENTS. NEC 110.16, 110.22, 110.24 |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR NEW |
| | ELECTRIC SERVICE AND PANEL BOARDS. NEC 110.9, 110.10 |
| | |
| | INDICATE THE SIZE AND TYPE ELECTRICAL SERVICE |
| | CONDUCTORS PROPOSED FOR THE NEW SERVICE. NEC |
| | 310.15(B)(16) |
| | |
| | SHOW ALL REQUIRED ACCESS AND SAFE WORKING CLEARANCES |
| | FOR THE ELECTRICAL SERVICE, MAIN DISCONNECTS AND PANEL |
| | BOARDS. NEC 110.26 |
| | |
| | VERIFY THE DRINKING COOLER IS PROTECTED WITH AN |
| | ACCESSIBLE GFCI. NEC 422.52 |
| | |
| | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AT AN |
| | ACCESSIBLE LOCATION FOR SERVICING THE AIR CONDITIONING |
| | EQUIPMENT. NEC 210.63, 210.8(B) |
| | |
| | VERIFY THE RELOCATED WATER HEATER HAS AN ELECTRICAL |
| | DISCONNECT. NEC 422.31 |
| | |
| | ALTERATIONS TO THE INTERIOR LIGHTING SYSTEM OF AN |
| | EXISTING BUILDING ARE SUBJECT TO THE REQUIREMENTS OF |
| | THE FLORIDA ENERGY CODE. THIS TYPICALLY INCLUDES THE |
| | USE OF OCCUPANCY SENSORS AND LIGHTING CONTROLS. THE |
| | PLAN NEEDS TO PROVIDE A SCOPE OF WORK THAT SPECIFICALLY |
| | ADDRESSES THE ENERGY CODE REQUIREMENTS. FBC EB 711, FBC |
| | C405 |
| | |