2017-04-18 15:16:59PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. INDICATED THE VOLTAGE FOR THE ELECTRICAL
 SERVICE. BOTH 240 VOLT AND 208 VOLTS ARE INDICATED ON
 THE DOCUMENTS. NEC 110.16, 110.22, 110.24
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR NEW
 ELECTRIC SERVICE AND PANEL BOARDS. NEC 110.9, 110.10
  
 INDICATE THE SIZE AND TYPE ELECTRICAL SERVICE
 CONDUCTORS PROPOSED FOR THE NEW SERVICE. NEC
 310.15(B)(16)
  
 SHOW ALL REQUIRED ACCESS AND SAFE WORKING CLEARANCES
 FOR THE ELECTRICAL SERVICE, MAIN DISCONNECTS AND PANEL
 BOARDS. NEC 110.26
  
 VERIFY THE DRINKING COOLER IS PROTECTED WITH AN
 ACCESSIBLE GFCI. NEC 422.52
  
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET AT AN
 ACCESSIBLE LOCATION FOR SERVICING THE AIR CONDITIONING
 EQUIPMENT. NEC 210.63, 210.8(B)
  
 VERIFY THE RELOCATED WATER HEATER HAS AN ELECTRICAL
 DISCONNECT. NEC 422.31
  
 ALTERATIONS TO THE INTERIOR LIGHTING SYSTEM OF AN
 EXISTING BUILDING ARE SUBJECT TO THE REQUIREMENTS OF
 THE FLORIDA ENERGY CODE. THIS TYPICALLY INCLUDES THE
 USE OF OCCUPANCY SENSORS AND LIGHTING CONTROLS. THE
 PLAN NEEDS TO PROVIDE A SCOPE OF WORK THAT SPECIFICALLY
 ADDRESSES THE ENERGY CODE REQUIREMENTS. FBC EB 711, FBC
 C405
  