| Plan Review Notes For Permit 17040662 |
| Permit Number |
17040662 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-04-25 17:51:21 | MECHANICAL PROVISOS: | | | 4/25/17 | | | | | | THE PLAN IS APPROVED WITH EXCEPTION. FAILURE TO MAKE | | | CORRECTIONS AS NOTED BELOW WILL RESULT IN FAILED | | | INSPECTIONS. | | | | | | 1) PROVIDE SITE SPECIFIC SIGNED AND SEALED WIND LOAD | | | ENGINEERING FOR INSTALLATION OF THE RTU'S AND CURB | | | ADAPTERS. | | | | | | 2) CORRECT THE OUTSIDE AIR CALCULATIONS TO INDICATE THE | | | TOTAL AREAS THAT EACH UNIT IS CONDITIONING AND | | | SUPPLYING OUTSIDE AIR TO. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|