2017-04-17 14:26:581ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040662
 4/17/17
  
 1) ALLL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN- SECTION 107.2.1
 WPB AMENDMENTS TO THE FBC.
  
 2) WIND LOAD ENGINEERING AND WIND DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOPS MUST BE SUBMITTED BY A
 FL. LICENSED ENGINEER OR ARCHITECT- SECTION 301.15
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  
 3) COMMISSIONING OF THE REPLACED SYSTEMS IS REQUIRED.
 REFER TO SECTION C408.2 FBC-14 ENERGY CONSERVATION-
 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
  
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
  
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
 EXCEPTION: THE FOLLOWING SYSTEMS ARE EXEMPT FROM THE
 COMMISSIONING REQUIREMENTS:
  
 1. MECHANICAL SYSTEMS IN BUILDINGS WHERE THE TOTAL
 MECHANICAL EQUIPMENT CAPACITY IS LESS THAN 480,000
 BTU/H (140 690 W) COOLING CAPACITY AND 600,000 BTU/H
 (175 860 W) HEATING CAPACITY.
  
 2. SYSTEMS INCLUDED IN SECTION C403.3 THAT SERVE
 DWELLING UNITS AND SLEEPING UNITS IN HOTELS, MOTELS,
 BOARDING HOUSES OR SIMILAR UNITS.
  
 C408.2.1 COMMISSIONING PLAN.
  
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A REGISTERED
 DESIGN PROFESSIONAL OR APPROVED AGENCY AND SHALL
 INCLUDE THE FOLLOWING ITEMS:
  
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
  
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
  
 3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED
 TO CALIBRATIONS AND ECONOMIZER CONTROLS.
  
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
 DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
  
 5. MEASURABLE CRITERIA FOR PERFORMANCE.
  