 E3405.4 LOCATION OF WORKING SPACES AND EQUIPMENT.
 REQUIRED WORKING SPACE SHALL NOT BE DESIGNATED FOR
 STORAGE. PANELBOARDS AND OVERCURRENT PROTECTION DEVICES
 SHALL NOT BE LOCATED IN CLOTHES CLOSETS, IN BATHROOMS,
 OR OVER THE STEPS OF A STAIRWAY.
  
 E3706.2 PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF
 THE PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR.
 CIRCUITS SHALL NOT BE DESCRIBED IN A MANNER THAT
 DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
  
 E3901.7 OUTDOOR OUTLETS.
 AT LEAST ONE RECEPTACLE OUTLET THAT IS ACCESSIBLE WHILE
 STANDING AT GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE. BALCONIES,
 DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM INSIDE OF
 THE DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE
 OUTLET INSTALLED WITHIN THE PERIMETER OF THE BALCONY,
 DECK, OR PORCH. THE RECEPTACLE SHALL BE LOCATED NOT
 MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY,
 DECK, OR PORCH SURFACE.
  
 R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES
 .
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE
 FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE
 FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY
 EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING
 DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED
 LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND
 TYPE OF CONDUCTORS TO BE USED.
  