| 2017-05-18 07:17:53 | 2014 FBC- BUILDING PLAN REVIEW BUILDING |
| | W. P. B. PERMIT: 17040620 |
| | ADD: 780 S. SAPODILLA AVE. SUITE # 214 |
| | CONT: LOWES HOME CENTERS |
| | TEL: 561-721-5611 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) ************* WITH RESPECT TO EVALUATION |
| | OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL |
| | GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE |
| | COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A |
| | PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE |
| | THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE |
| | VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH |
| | REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE |
| | PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. MAY 18/ 2017 |
| | ACTION: DENIED |
| | |
| | THE SUBMITTED TEST REPORTS FOR FLOOR SOUND INSULATION |
| | SELITBLOCK 2 TEST ASTM E 492-09 & ASTM E 90 BOTH ARE |
| | CODE COMPLIANT FOR A 6 INCH CONCRETE SLAB. |
| | MISSING IS THE FLAME SPREAD TESTING REPORT. |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 3RD REQUEST!!!!! C) FLAME SPREAD- FBC-B 2014 603.1. |
| | EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| | SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | COMPLIED. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | COMPLIED. FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |