| Plan Review Notes For Permit 17040553 |
| Permit Number |
17040553 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-28 11:09:37 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. ON THE RISER THE SHOWER AND TOILET IN THE MASTER | | | BATHROOM ARE NOT VENTED THEY SHALL CONNECT TO THE WET | | | VENT OF THAT BATHROOM GROUP ALONG WITH THE TWO | | | LAVATORY'S AND THE TUB. PER FBC RES P3108.1 | | | | | | 2. THE 2" VENT THROUGH THE ROOF BETWEEN THE TOILET AND | | | SHOWER IS NOT A REQUIRED VENT IT SHALL NOT RUN | | | HORIZONTAL IT SHALL CONNECT TO BRANCH DRAIN ABOVE THE | | | CENTER LINE OF THE DRAIN AND RUN AT A 45 DEGREE ANGLE | | | UP TO A POINT ABOVE THE FLOOD LEVEL RIM OF THE FIXTURES | | | IT SERVES. PER FBC RES P3104.3 , P3104.4 | | | | | | 3. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL | | | STACK. PER FBC RES P3005.2.6 | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|