| Plan Review Notes For Permit 17040515 |
| Permit Number |
17040515 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-05 18:53:31 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ( PREVIOUS COMMENT )THE ENERGY FORM R405-2014 IS | | | REQUIRED TO BE SIGNED AND DATED BY THE OWNER/AGENT. FBC | | | ENERGY CONSERVATION R103.1.1.2 | | | | | | 2) ADDRESSED. | | | | | | 3) ADDRESSED. | | | | | | 4) ( TO BE DEFERED TO A LATER DATE AT OWNER'S REQUEST - | | | PREVIOUS COMMENT ) FBC 107.3.4 - PROVIDE TWO SETS OF | | | PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE | | | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE WINDOW/GLASS TYPES AND EXTERIOR DOOR | | | TYPES. |
|