2017-05-10 09:19:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM R405-2014 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 R103.1.1.2
  
 2) PROVIDE A ROOF FRAMING PLAN AND SHEATHING DETAILS
 FOR THE ADDITION OF THE 4 FEET TO BEDROOM NUMBER 3.
 FBC-R802.2 & R803
  
 3) PROVIDE EXISTING AND A PROPOSED AREA TABULATIONS.
 THE PROPERTY APPRAISER SPECIFIES THAT THERE IS 1342
 SQFT UNDER AIR AND DOES NOT INCLUDE THE 230 SQFT
 ENCLOSED PORCH. THE CARPORT STORAGE WILL NO LONGER BE
 100 SQFT WHEN PART OF IT IS CONVERTED TO A WALK IN
 CLOSET. ALSO INCLUDE THE 4' X 11' 8" ADDITION TO
 BEDROOM NUMBER 3. FBC 107.2.1
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.