| Plan Review Notes For Permit 17040490 |
| Permit Number |
17040490 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-13 13:29:09 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE DESIGN PRESSURES ON SHEET 8.5 ARE: | | | | | | ZONE 4: +52, -52 | | | ZONE 5: +52, -95.7. | | | | | | THE DP LIMITATION FOR THE PROPOSED DOOR IS +-65PSF. IT | | | IS NOT CLEAR IF ANY OF THE DOORS PROPOSED ARE LOCATED | | | IN, OR PARTIALLY LOCATED IN, ZONE 5. | | | | | | PROVIDE A PLAN SHOWING THE LOCATIONS OF PROPOSED DOORS, | | | FEET FROM THE CORNER. IF ANY DOORS ARE PARTIALLY IN | | | ZONE 5, DESIGN PRESSURE FOR THE OPENING TO BE SPECIFIED | | | BY THE ENGINEER, OR SUBMIT A PRODUCT APPROVAL FOR A | | | DOOR WHICH MEETS THE REQUIREMENT FOR ZONE 5. | | | | | | |
|