Plan Review Notes
Plan Review Notes For Permit 17040484
Permit Number 17040484
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-13 15:08:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE APPLICATION STATES "ADDED ONE SPRINKLER HEAD".
 THE IS NO INDICATION ON THE SUBMITTED PLAN WHERE THE
 ADDED SPRINKLER HEAD IS LOCATED.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
  
 PLEASE PROVIDE A REVISION CLOUD OR OTHER SPECIFIC
 CALL-OUT OF WHERE THE ADDED SPRINKLER HEAD IS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  