| Plan Review Notes For Permit 17040484 |
| Permit Number |
17040484 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-13 15:08:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THE APPLICATION STATES "ADDED ONE SPRINKLER HEAD". | | | THE IS NO INDICATION ON THE SUBMITTED PLAN WHERE THE | | | ADDED SPRINKLER HEAD IS LOCATED. | | | | | | PER NFPA 1 | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | | | | PLEASE PROVIDE A REVISION CLOUD OR OTHER SPECIFIC | | | CALL-OUT OF WHERE THE ADDED SPRINKLER HEAD IS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|