Plan Review Notes
Plan Review Notes For Permit 17040472
Permit Number 17040472
Review Stop M
Sequence Number 2
Notes
Date Text
2017-05-10 09:19:432ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040472
 5/10/17
  
 RESULTS: DENIED.
  
 1) THE REQUESTED AC CALCULATIONS AND CORRECTED
 MECHANICAL PLANS WERE NOT SUBMITTED- SEE 1ST REVIEW
 COMMENTS REPRINTED BELOW.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040472
 4/14/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) A DUCT SMOKE DETECOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF AHU-1 UNLESS MANUFACTURER'S SPECIFICATIONS
 INDICATE THE UNIT IS INCAPABLE OF PRODUCING OVER 2000
 CFM'S OF SUPPLY AIR.
  
 3) M002: CORRECT THE SYSTEM IDENTIFICATION IN THE O/A
 SCHEDULE FROM RTU-1 TO AHU-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  