| Plan Review Notes For Permit 17040472 |
| Permit Number |
17040472 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-10 09:19:43 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040472 | | | 5/10/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE REQUESTED AC CALCULATIONS AND CORRECTED | | | MECHANICAL PLANS WERE NOT SUBMITTED- SEE 1ST REVIEW | | | COMMENTS REPRINTED BELOW. | | | | | | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040472 | | | 4/14/17 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION | | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | 2) A DUCT SMOKE DETECOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM OF AHU-1 UNLESS MANUFACTURER'S SPECIFICATIONS | | | INDICATE THE UNIT IS INCAPABLE OF PRODUCING OVER 2000 | | | CFM'S OF SUPPLY AIR. | | | | | | 3) M002: CORRECT THE SYSTEM IDENTIFICATION IN THE O/A | | | SCHEDULE FROM RTU-1 TO AHU-1. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|