2017-04-27 09:15:161ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS FOR ACCESSIBLE BATHROOM.
 PER WPB AMEND TO FBC 107.2.1
  
 2. SHOW CLEAR FLOOR SPACE FOR LAVATORY AND TOILET. PER
 FBC ACC 604.3.1 AND 606.2
  
 3. SHOW COMPLIANCE WITH HEIGHT OF THE WATER CLOSET. PER
 FBC ACC 604.4
  
 4. THE TOILET PAPER DISPENSER SHALL BE 7"- 9" FROM THE
 FRONT OF THE TOILET THE PLAN SHOWS 4"- 9" PLEASE
 CLARIFY. PER FBC ACC 604.7
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC ACC 416.5
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  