2017-04-15 04:44:411) PLANS DONE IN PENCIL ARE UNACCEPTABLE. SUBMIT TWO
 COPIES OF THE PLAN THAT ARE DONE IN AN UNERASABLE
 FORMAT. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUAL FOR THE LIFT
 STATION. WPB AMEND. TO FBC SEC. 107.2.1.
 3) A CHECK VALVE AND FULL OPEN VALVE LOCATED ON THE
 DISCHARGE SIDE OF THE CHECK VALVE IS REQUIRED PER 2014
 FBC-PLUMBING SEC.712.2. ACCESS SHALL BE PROVIDED TO
 SUCH VALVES.
 4) THE SUMP DESIGN SHALL COMPLY WITH 2014 FBC- PLUMBING
 SEC.712.3.
 5) THE LIFT STATION DISCHARGE CONNECTION TO THE 4"
 SEWER SHALL COMPLY WITH 2014 FBC - PLUMBING
 SEC.712.3.5.
 6) INDICATE ON THE PLAN IF ANY TUNNELING WILL BE
 REQUIRED UNDER THE EXISTING STRUCTURE IN ORDER TO WORK
 ON THE EXISTING KITCHEN DRAIN. IF SO, DETAILS AND
 BACKFILLING PROCEDURES SHALL BE SUBMITTED THAT CLEARLY
 SHOW HOW THE STRUCTURAL INTEGRITY OF THE CONCRETE SLAB
 WILL BE MAINTAINED DURING EXCAVATION AND BACKFILLING.
 STRUCTURAL FOAM IS NOT PERMITTED BELOW GROUND PER THE
 FLORIDA BUILDING CODE, RESIDENTIAL, SECTION 318 AND THE
 FLORIDA BUILDING CODE, BUILDING, SECTION 2603.8.
 7) A CLEANOUT IS REQUIRED IN THE 2 INCH LINE PER 2014
 FBC- PLUMBING SEC.708.3.2.
 8) THE LIFT STATION WILL REQUIRE ELECTRIC. WHAT
 PROVISIONS ARE BEING DONE TO PROVIDE ELECTRIC TO THE
 UNIT? INDICATE ON THE PLANS. WPB AMEND. TO FBC SEC.
 107.2.1.
  