| 2017-06-02 10:00:06 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | REVIEW COMMENTS: |
| | |
| | 1. PROVIDE CORRECTION FOR EXTERIOR LIGHTS. FOR DWELLING |
| | UNITS, ATTACHED GARAGES, AND DETACHED GARAGES WITH |
| | ELECTRIC POWER, AT LEAST ONE WALL SWITCH-CONTROLLED |
| | LIGHTING OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE |
| | OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. |
| | NEC 210.70(A)(2)(B), FBC RE3903.3 |
| | 2. PROVIDE CORRECTION FOR AFCI PROTECTION. ALL |
| | 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| | DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| | PROTECTION. NEC 210.12, FBC RE3902.12 |
| | 3. PROVIDE CORRECTION FOR MASTER CLOSET LIGHTING. |
| | LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| | PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOSETS. NEC 410.16(B), FBC RE4003.12 |
| | 4. PROVIDE CORRECTION FOR LIGHT OVER JACUZZI. LIGHTING |
| | IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE FOR DAMP |
| | OR WET LOCATIONS AS REQUIRED. NEC 410.10(A), FBC |
| | RE4003.11 |
| | 5. PROVIDE CORRECTION FOR POWER TO JACUZZI. |
| | HYDROMASSAGE TUBS AND THEIR ASSOCIATED EQUIPMENT SHALL |
| | BE ON AN INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED AND |
| | PROTECTED BY A READILY-ACCESSIBLE GFCI. NEC 680.71, FBC |
| | RE4209.1 |
| | 6. PROVIDE CORRECTION FOR MASTER BATH OUTLETS. A GFCI |
| | PROTECTED OUTLET IS REQUIRED WITHIN 36" OF EACH BASIN. |
| | NEC 210.52(D), FBC RE3901.6 |
| | 7. PROVIDE CORRECTION FOR KITCHEN PENINSULA. A GFCI |
| | PROTECTED OUTLET IS REQUIRED FOR THE COUNTER SPACE ON A |
| | PENINSULA. NEC 201.52(C)(3), FBC RE3901.4.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |