| 2017-06-20 08:30:31 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SQUARE FOOTAGE OF ATTACHED GARAGE STATED AS 300 SQ. |
| | FT. (SEE ELEVATION CERTIFCATE A9 A). THIS SHOULD BE 464 |
| | SQ. FT. |
| | 2. SCOPE OF WORK INCREASED TO INCLUDE THE INSTALLATION |
| | OF FLOOD VENTS. |
| | 3. IF ENGINEERED VENTS ARE INSTALLED, PROVIDE DESIGN |
| | CERTIFIED BY A REGISTERED DESIGN PROFESSIONAL OR AN |
| | EVALUATION REPORT ISSUED BY THE INTERNATIONAL CODE |
| | COUNCIL (ICC) EVALUATION SERVICE, INC. |
| | 4. IF NON-ENGINEERED OPENINGS ARE INSTALLED, REFER TO |
| | FEMA'S NON-ENGINEERED OPENING GUIDE, VOLUME 1 DATED |
| | JANUARY 2015. |
| | 5. LOCATION OF PROPOSED VENTS ARE ON ONE WALL. REFER TO |
| | FEMA'S OPENINGS IN FOUNDATION WALLS AND WALLS OF |
| | ENCLOSURES TECHNICAL BULLENTIN 1 DATE AUGUST 2008. IT |
| | IS RECOMMENDED THAT OPENINGS BE REASONBLY DISTRIBUTED |
| | AROUND THE PEREMITER OF THE ENCLOSED AREA UNLESS THERE |
| | IS CLEAR JUSTIFICATION FOR PUTTING ALL OPENINGS ON JUST |
| | ONE OR TWO SIDES. THERE APPEARS TO BE AN AREA LOCATED |
| | ADJACENT TO THE FOYER EXTERIOR DOOR TO LOCATE AT LEAST |
| | ONE VENT. |
| | 6. FINAL ELEVATION CERTIFCATE REQUIRED PRIOR TO FINAL |
| | INSPECTION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |