| 2017-05-04 18:43:23 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2948-R11: |
| | MECHANICALLY ATTACHED BASE SHEET NEEDS WITHDRAWAL |
| | RESISTANCE TEST (TAS 105) AS REQUIRED BY NOTE #10 ON |
| | PAGE 2 OF 52 OF FLORIDA PRODUCT APPROVAL SUBMITTED. |
| | PROVIDE 2 COPIES. NOTE: THIS APPLIES TO THE |
| | ADMINISTRATION BUILDING AND TO THE PUMP BUILDING. |
| | SEC. 1609 FBC. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2-ENGINEER RAS 117 CALCULATIONS SUBMITTED: |
| | A) CALCULATIONS REFERENCE THE FBC 2010. THE CURRENT |
| | CODE IS FBC 5TH EDITION (2014). REVISE AS REQUIRED. |
| | CHAPTER 553 F.S. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) THE BUILDING EXPOSURE FOR THIS BUILDINGS IS "D" NOT |
| | "C". REVISE THE BUILDING EXPOSURE AND CORRESPONDING |
| | COEFFICIENTS AS REQUIRED. SEC. 1609.4 FBC, 5TH EDITION |
| | (2014). |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) THE BUILDING RISK CATEGORY FOR THIS BUILDING ARE NOT |
| | RISK CATEGORY II. SEE RISK CATEGORY TABLE 1604.5 OF |
| | FBC- 5TH EDITION (2014) AND REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D) ENGINEER TO PROVIDE CALCULATIONS WITH ORIGINAL SEAL |
| | AND SIGNATURE AS REQUIRED BY CHAPTER 471 F.S.. THIS IS |
| | NOT A DIGITAL SUBMITTAL, NEED THE ORIGINAL SEAL AND |
| | SIGNATURE. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | E) ENGINEER TO COORDINATE CALCULATIONS WITH ITEM #1 |
| | ABOVE. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- NEW METAL ROOF FLORIDA PRODUCT APPROVAL FL16317-R1 |
| | SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. 1609 FBC. NOTE: PLEASE MAKE |
| | SURE SELECTED ASSEMBLY MEETS THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES. THE DESIGN PRESSURES OF SOME ASSEMBLIES |
| | ARE LOW AND CAN NOT BE USED FOR ZONE #3 ON EXPOSURE |
| | "D". |
| | |
| | NOTE: BUILDING IS LOCATED IN EXPOSURE "D". |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |