| Plan Review Notes For Permit 17040372 |
| Permit Number |
17040372 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-15 04:21:22 | 1) SHOW ALL PIPE SIZES OF THE DRAIN LINES ON THE | | | PLUMBING DRAWINGS. | | | 2) SUBMIT SIZING CALCULATIONS FOR THE SIZE OF THE | | | GREASE TRAP BEING INSTALLED. 2014 FBC-PLUMBING SEC. | | | 1003.2. CALCULATIONS SHALL BE DONE IN ACCORDANCE WITH | | | 2014 FBC-PLUMBING SEC.1003.3.4. | | | 3) THE CAPACITY OF THE GREASE TRAP SHALL COMPLY WITH | | | 2014 FBC-PLUMBING TABLE 1003.3..4.1. | | | 4) INDICATE THE SIZE OF THE UNIT ON BOTH COPIES OF THE | | | SPECIFICATIONS FROM ZURN. | | | 5) PLACE THE ADDRESS & UNIT NUMBER OF THE SPACE ON THE | | | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|