2017-05-24 09:02:091ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE VENTS THAT WHERE ADDED TO THE WATER CLOSETS AND
 TUBS ON THE GROUND FLOOR ARE HORIZONTAL DRY VENTS WHICH
 ARE NOTE ALLOWED PER FBC PL 905.3 THE WATER CLOSET AND
 TUB COULD CONNECT TOGETHER TO A BRANCH VENTED BY THE
 LAVATORY. PER FBC PL 912.1
  
 2. CLEAN OUTS ARE MISSING ON THE BASE OF THE SOIL
 STACK. PER FBC PL 708.3.4
  
 3. PLEASE PROVIDE MANUFACTURE SPEC SHEETS FOR THE
 TANKLESS WATER HEATERS. PER WPB AMEND TO FBC
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  