| Notes |
| Date |
Text |
| 2017-04-28 17:14:03 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE TOILETS AND TUBS ON THE FIRST FLOOR NEED TO BE | | | VENTED BEFORE THEY CONNECT TO BUILDING DRAIN. PER FBC | | | PL 901.2.1 | | | | | | 2. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL AND | | | WASTE STACKS. PER FBC PL 708.3.4 | | | | | | 3. PROVIDE WATER RISER .PER WPB AMEND TO FBC | | | 107.3.5.1.3(13) | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|