2017-04-28 17:14:031ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE TOILETS AND TUBS ON THE FIRST FLOOR NEED TO BE
 VENTED BEFORE THEY CONNECT TO BUILDING DRAIN. PER FBC
 PL 901.2.1
  
 2. A CLEAN OUT IS REQUIRED AT THE BASE OF THE SOIL AND
 WASTE STACKS. PER FBC PL 708.3.4
  
 3. PROVIDE WATER RISER .PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  