| Plan Review Notes For Permit 17040361 |
| Permit Number |
17040361 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-02 12:29:55 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | SERVICE MAINS TO BE GROUPED 230.72, FBCRE3601.7 | | | | | | FBCRE3903.3 ADDITIONAL LOCATIONS. | | | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED | | | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT | | | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL | | | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR | | | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL | | | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED | | | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A | | | VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN | | | OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS | | | ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A | | | WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT | | | INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS | | | WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE | | | RISERS. | | | FRONT OF "A" AND "B" | | | | | | UNIT "A" | | | SMOKE ALARM AT BOTTOM OF THE STAIRS | | | OUTLET ON FRONT OUTSIDE | | | OUTLET SPACING PER CODE | | | | | | UNIT "B" | | | OUTLET AT FRONT OUTSIDE | | | COUNTER OUTLET BY FRIDGE TO BE GFCI PROTECTED | | | OUTLET SPACING PER CODE | | | | | | | | | | | | | | | |
|