Plan Review Notes
Plan Review Notes For Permit 17040338
Permit Number 17040338
Review Stop P
Sequence Number 1
Notes
Date Text
2017-04-24 11:40:471ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. D2.0 SHOWS 40 GAL EXISTING WATER HEATER AND HAS
 A NOTE TO BE REPLACED THE REAST OF THE PLAN SHOWS 65
 GAL EXISTING IT IS SHOWN ON SHT P1.1 AS EXISTING PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE LABEL RISER DIAGRAMS. PER WPB AMEND TO FBC
 107.2.1
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  