| Plan Review Notes For Permit 17040338 |
| Permit Number |
17040338 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-24 11:40:47 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. D2.0 SHOWS 40 GAL EXISTING WATER HEATER AND HAS | | | A NOTE TO BE REPLACED THE REAST OF THE PLAN SHOWS 65 | | | GAL EXISTING IT IS SHOWN ON SHT P1.1 AS EXISTING PLEASE | | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE LABEL RISER DIAGRAMS. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|