| Plan Review Notes For Permit 17040336 |
| Permit Number |
17040336 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-15 03:30:44 | 1) THE SUBMITTED "SCOPE OF WORK" NOTES ARE MOSTLY | | | ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE NARRATIVE THAT | | | OUTLINES THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 2) INDICATE THE LEVEL OF ALTERATION ON THE PLANS AND | | | THE METHOD OF COMPLIANCE IN ACCORDANCE WITH THE 2014 | | | FBC-EXISTING BUILDING CODE SEC. 301.1. | | | 3) INDICATE ON THE PLAN IF THE BASE CABINETS WITH SINKS | | | ARE BEING REPLACED IN ANY OF THE EXAM ROOMS. IF | | | CABINETS ARE BEING REPLACED, AT LEAST ONE EXAM ROOM | | | BASE CABINET WITH A SINK SHALL COMPLY WITH 2014 | | | FBC-ACCESS. SEC.212.3. | | | 4) A BUSINESS OCCUPANCY IS REQUIRED TO HAVE A DRINKING | | | FOUNTAIN. PREVIOUS PERMIT # 09110083 SHOWED A DRINKING | | | FOUNTAIN IN THE RECEPTION AREA.WHERE IS THE DRINKING | | | FOUNTAIN IN THIS SPACE? IF IT HAS BEEN REMOVED A | | | MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER THE | | | 2014 FBC-ACCESS. SEC.211.2.AND TABLE 403.1 OF THE | | | FBC-PLUMBING CODE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|