| Plan Review Notes For Permit 17040294 |
| Permit Number |
17040294 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-05-02 13:32:05 | RESIDENTIAL (R3) SUBMITTAL, BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- TREMCO BUILT UP ROOFING SYSTEM OVER CONCRETE DECK | | | NOA 16-092.16 SUBMITTED: | | | A) CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: NEED ASSEMBLY THAT IS DESIGNED TO RECEIVE STONE | | | AS SHOWN ON PLANS. ALSO, IF THE DESIGN PRESSURES OF THE | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES OF | | | ALL ROOF DECK ZONES, THEN IT CAN NOT BE USED BECAUSE | | | ALL THE SYSTEMS IN THIS NOA ARE LIMITED BY GENERAL | | | LIMITATION # 9. THIS LIMITATION STATES THAT LISTED | | | DESIGN PRESSURES IS APPLICABLE TO ALL ROOF ZONES. IT | | | DOESN'T ALLOW FOR RATIONAL ANALYSIS OR EXTRAPOLATION | | | FOR ENHANCED FASTENING. SEE GENERAL LIMITATION #9 ON | | | LAST PAGE OF NOA SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|