| Plan Review Notes For Permit 17040268 |
| Permit Number |
17040268 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-13 08:23:17 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040268 | | | 4/13/17 | | | | | | 1) SHEET DT1.0: THE STRUCTURAL NOTES PROVIDE ARE NOT | | | PROVIDING EVIDENCE OR DATA TO INDICATETHE DISPENSERTS | | | WILL BE ANCHORED TO WITHSTAND 170 MPH WIND LOADS AND | | | ASSOCIATRED LATERAL AND UPLIFT PRESSURES- SECTION | | | 301.15 FBC-14 MECHANICAL. | | | | | | 2) SUBMIT MANUFACTURWER'S SPECIFICATIONS FOR THE | | | DISPENSERS AND HOSES WITH SHOP DRAWING APPOVAL STAMPS | | | BY THE ENGINEER OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|