Plan Review Notes
Plan Review Notes For Permit 17040268
Permit Number 17040268
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-13 08:23:171ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040268
 4/13/17
  
 1) SHEET DT1.0: THE STRUCTURAL NOTES PROVIDE ARE NOT
 PROVIDING EVIDENCE OR DATA TO INDICATETHE DISPENSERTS
 WILL BE ANCHORED TO WITHSTAND 170 MPH WIND LOADS AND
 ASSOCIATRED LATERAL AND UPLIFT PRESSURES- SECTION
 301.15 FBC-14 MECHANICAL.
  
 2) SUBMIT MANUFACTURWER'S SPECIFICATIONS FOR THE
 DISPENSERS AND HOSES WITH SHOP DRAWING APPOVAL STAMPS
 BY THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  