2017-04-27 12:55:061ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE CLARIFY IS ENTIRE SANITARY SYSTEM BEING
 REPLACED THE THE RISER DOES NOT INDICATE EXISTING OR
 NEW ONLY THE NEW PIPING IS REQUIRED TO BE ON THE PLAN.
 PER WPB AMEND TO FBC 107.2.1
  
 2. IS THIS UNIT ABOVE GROUND LEVEL IF IT IS GROUND
 LEVEL PLEASE SHOW THE FIXTURE CONNECTED TO THE
 HORIZONTAL DRAIN AND NOT THE VERTICAL STACK. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE LAUNDRY TRAY AND WASHING MACHINE CAB NOT BE
 VENTED TOGETHER WITH THE TOILET. THE TOILET SHOULD BE
 INDIVIDUALLY VENTED OR CONNECT TO THE BATHROOM GROUP.
 PER FBC PL 912.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  