2017-05-10 14:59:001ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17040262
 5/10/17
  
 RESULTS: DENIED
  
 1) THE PLAN SHOWS A 16" MAIN RETURN DUCT PENETRATING
 INTO THE AIR HANDLER CLOSET, HOWEVER THE AIR HANDLER
 CLOSET DETAIL DOES NOT SHOW THE DUCT. PLEASE CLARIFY
 HOW THE RETURN AIR SYSTEM IS FUNCTIONING.
  
 2) SHOW THE REQUIRED CLEARANCES FOR THE AIR HANDLER IN
 THE CLOSET- 3" ALONG THE SIDES, BACK AND TOP, WITH THE
 TOTAL WIDTH OF THE CLOSET AT LEAST 12" WIDER THAT THE
 AIR HANDLER- SECTION M1305.1.1.
  
 3) PROVIDE THE BEDROOM TRANSFER DUCT SIZES- SEE SECTION
 M1602.4.
  
 4) PROVIDE KITCHEN EXHAUST AT A RATE OF 100 CFM
 INTERMITTENT OR 25 CFM CONTINUOUS- TABLE 1507.4.
  
 5) THE BATH EXHAUST FAN CAPACITIY SHALL BE MINIMUM 50
 CFM INTERMITTENT OR 20 CFM CONTINUOUS- TABLE 1507.4.
  
 6) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGY
 CONSERVATION FORM R405-2014.
  
 7) SHOW THE TYPE AND SIZE OF DRYER EXHAUST DUCT AND
 TERMINATION LOCATION- SECTION M1502.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  