| Plan Review Notes For Permit 17040262 |
| Permit Number |
17040262 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-10 14:59:00 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17040262 | | | 5/10/17 | | | | | | RESULTS: DENIED | | | | | | 1) THE PLAN SHOWS A 16" MAIN RETURN DUCT PENETRATING | | | INTO THE AIR HANDLER CLOSET, HOWEVER THE AIR HANDLER | | | CLOSET DETAIL DOES NOT SHOW THE DUCT. PLEASE CLARIFY | | | HOW THE RETURN AIR SYSTEM IS FUNCTIONING. | | | | | | 2) SHOW THE REQUIRED CLEARANCES FOR THE AIR HANDLER IN | | | THE CLOSET- 3" ALONG THE SIDES, BACK AND TOP, WITH THE | | | TOTAL WIDTH OF THE CLOSET AT LEAST 12" WIDER THAT THE | | | AIR HANDLER- SECTION M1305.1.1. | | | | | | 3) PROVIDE THE BEDROOM TRANSFER DUCT SIZES- SEE SECTION | | | M1602.4. | | | | | | 4) PROVIDE KITCHEN EXHAUST AT A RATE OF 100 CFM | | | INTERMITTENT OR 25 CFM CONTINUOUS- TABLE 1507.4. | | | | | | 5) THE BATH EXHAUST FAN CAPACITIY SHALL BE MINIMUM 50 | | | CFM INTERMITTENT OR 20 CFM CONTINUOUS- TABLE 1507.4. | | | | | | 6) THE OWNER/AGENT MUST SIGN AND DATE THE ENERGY | | | CONSERVATION FORM R405-2014. | | | | | | 7) SHOW THE TYPE AND SIZE OF DRYER EXHAUST DUCT AND | | | TERMINATION LOCATION- SECTION M1502. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|