Plan Review Notes
Plan Review Notes For Permit 17040262
Permit Number 17040262
Review Stop E
Sequence Number 1
Notes
Date Text
2017-04-21 11:30:39INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 2. SHOW EXTERIOR RECEPTACLE AT FRONT/BACK ENTRANCE TO
 MAIN HOUSE PROTECTED BY GFCI DEVICE. FBC RES E3902.3
 3. PLEASE ADDRESS WALL SPACE RECEPTACLE REQUIREMENTS
 PER FBC RES E3901.2.2, 1. ANY SPACE THAT IS 2FT OR MORE
 IN WIDTH. SEE BEDROOM #5.
 4. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET/
 MAIN HOUSE
 5. RECEPTACLE AT THE LAUNDRY ROOM 6FT OF SINK TO BE
 LABELED AS GFCI PROTECTED. FBC RES E3902.7
 6. THERE NEEDS TO BE 3FT. CLEARANCE IN FRONT OF PANELS
 A AND B. DOESN?T APPEAR TO BE.
 7. SHOW LIGHTING OUTLET AT THE ATTIC ACCESS LOCATION
 PER FBC RES E3903.4
 8. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  