| Plan Review Notes For Permit 17040259 |
| Permit Number |
17040259 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-12 12:21:58 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | | AND EXISTING BUILDING CODES | | | PERMIT #17040259 | | | 6/12/17 | | | | | | RESULTS: DENIED. | | | | | | 1) THE SUBMITTED ENERGYGAUGE COMPLIANCE REPORT AND AC | | | CALCULATIONS APPEAR TO BE FOR ONLY THE FIRST FLOOR | | | OCCUPANCY. PLEASE INCLUDE THE ENERGY COMPLIANCE DATA | | | AND AC CALCULATIONS FOR THE SECOND FLOOR IN THE | | | SUBMITTAL. | | | | | | 2) CORRECT THE CLASSIFICATION OF "NEW FINISHED | | | BUILDING" IN THE ENERGYGAUGE PROJECT SUMMARY ON PAGE 2. | | | THIS IS A RENOVATION AND CHANGE OF OCCUPANCY. | | | | | | 3) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS FOR THE | | | NEW AND EXISTING SYSTEMS. INCLDE THE MAKES AND MODELS, | | | COOLING AND HEATING CAPACITIES, HEATING KW'S, AND | | | EFFICIENCY RATINGS. | | | | | | 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|