Plan Review Notes
Plan Review Notes For Permit 17040259
Permit Number 17040259
Review Stop M
Sequence Number 2
Notes
Date Text
2017-06-12 12:21:582ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 AND EXISTING BUILDING CODES
 PERMIT #17040259
 6/12/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGYGAUGE COMPLIANCE REPORT AND AC
 CALCULATIONS APPEAR TO BE FOR ONLY THE FIRST FLOOR
 OCCUPANCY. PLEASE INCLUDE THE ENERGY COMPLIANCE DATA
 AND AC CALCULATIONS FOR THE SECOND FLOOR IN THE
 SUBMITTAL.
  
 2) CORRECT THE CLASSIFICATION OF "NEW FINISHED
 BUILDING" IN THE ENERGYGAUGE PROJECT SUMMARY ON PAGE 2.
 THIS IS A RENOVATION AND CHANGE OF OCCUPANCY.
  
 3) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 NEW AND EXISTING SYSTEMS. INCLDE THE MAKES AND MODELS,
 COOLING AND HEATING CAPACITIES, HEATING KW'S, AND
 EFFICIENCY RATINGS.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER