| 2017-04-11 14:55:07 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040259 | | | 4/11/17 | | | | | | 1) REFER TO SECTION C403.2.1 FBC-14 ENERGY CONSERVATION | | | AND PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW AC SYSTEMS. | | | | | | 2) ENERGYGAUGE COMPLIANCE FORM: PLEASE PROVIDE SYSTEM | | | IDENTIFICATION NUMBERS THAT MATCH THE IDENTIFICATION | | | NUMBERS ON THE PLANS. | | | | | | 3) SHEET M-2: PROVIDE A DUCT SMOKE DETECTOR IN THE | | | RETURN AIR SYSTEM OF AHU-1- SECTION 606.2.1 FBC-14 | | | MECHANICAL. PLEASE NOTE THAT A TYPICAL 5-TON AC SYSTEM | | | WILL EXCEED 2000 CFMS SUPPLY AIR. | | | | | | 4) M-2: PROVIDE AUTOMATIC SHUTOFF DAMPERS FOR THE O/A | | | DUCTS SERVING AHU-1 & 2- SECTION 403.2.4.4 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 5) M-4: PROVIDE MANUFACTURER'S SPECIFICATIONS (CUT | | | SHEET) FOR THE FASSON #9150 STRAPPING TAPE THAT | | | INDICATES COMPLIANCE WITH SMACNA STANDARDS. | | | | | | 6) M-4: THE CONDENSER ANCHORING DETAIL HAS A COPIED, | | | OUTDATED ENGINEER'S SEAL, AND IS BASED ON AN OUTDATED | | | WIND SPEED. PLEASE SEE SECTION 1609 FBC-14 BUIILDING | | | AND PROVIDE CURRENT CODE COMPLIANT ENGINEERING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|