| Date |
Text |
| 2017-04-13 10:41:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET CS 1 - MULTIPLE OCCUPANCIES ARE INDICATED; |
| | HOWEVER, THE OCCUPANCY CLASSIFICATION IS NOT. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY |
| | TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY |
| | SHALL BE TREATED AS A MIXED OCCUPANCY. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| | RESISTANCE?RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE BUILDING COMPRISING A DISTINCT |
| | OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE |
| | COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, |
| | 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE |
| | 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY |
| | APPROVED EXISTING SEPARATIONS. |
| | |
| | |
| | PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND ENSURE |
| | COMPLIANCE WITH SEPARATION REQUIRERMENTS. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 1 - AN ELEVATOR ROOM IS INDICATED WITHIN THE |
| | STAIRWELL. PER NFPA 101, CHAPTER 7, MEANS OF EGRESS, |
| | |
| | 7.1.3.2.3* AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY |
| | PURPOSE THAT HAS THE POTENTIAL TO INTERFERE WITH ITS |
| | USE AS AN EXIT AND, IF SO DESIGNATED, AS AN AREA OF |
| | REFUGE. (SEE ALSO 7.2.2.5.3.) |
| | |
| | 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN |
| | EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER |
| | STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2. |
| | 7.2.2.5.3.1 OPEN SPACE WITHIN THE EXIT ENCLOSURE SHALL |
| | NOT BE USED FOR ANY PURPOSE THAT HAS THE POTENTIAL TO |
| | INTERFERE WITH EGRESS. |
| | 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED |
| | UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING |
| | CRITERIA ARE MET: |
| | (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| | ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT |
| | ENCLOSURE. |
| | (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| | FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.) |
| | (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE, |
| | OR OTHERWISE HAZARDOUS MATERIALS. |
| | |
| | THE DESIGN DOES NOT MEET THE CODE REQUIREMENTS. THERE |
| | IS NO RATING INDICATED FOR THE CEILING. THE ENTRANCE |
| | DOOR IS WITHIN THE ENCLOSURE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 3) SHEET LS 1 - THERE IS A LIGHTWEIGHT ROOF SIGN |
| | INDICATED; HOWEVER, A ROOF AND FLOOR (R/F) IS REQUIRED. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | 4) SHEETS LS 1 & 2 - THERE IS A NOTE INDICATING THE |
| | EGRESS CAPACITY AT THE 2ND FLOOR STAIWELL DOORS 36" AT |
| | .2 = 180; HOWEVER, PER NFPA 101 CHAPTER 7, .3 SHALL BE |
| | USED FOR STAIRWELLS. THOUGH NO DIMESION IS INDICATED, |
| | FOR REFERENCE PURPOSES; 36" AT .3 = 120. THE EGRESS |
| | CAPACITY IS THE LESSER OF THE TWO CALCULATIONS. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS |
| | SHOWN IN TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 . |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 1 - A NEW ELEVATOR IS INDICATED. PER NFPA 1 |
| | & 101, |
| | |
| | 11.3.1 FIRE FIGHTERS? EMERGENCY OPERATIONS. |
| | 11.3.1.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS. [101:9.4.3.1] |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLAINCE. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |