| 2017-05-11 11:29:55 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY | | | SUBMITTAL COMPLIANT WITH FBC-E 103 | | | | | | FBC-EC 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF | | | | | | FBC-EC 505.2.4 - PROVIDE A TIME CLOCK OR ASTRONOMICAL | | | SWITCH TO TURN OFF DURING DAYLIGHT HOURS. | | | | | | FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE SIZES | | | | | | |
|