Notes
Date Text
2017-05-11 11:29:55JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
  
 FBC-EC 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF
  
 FBC-EC 505.2.4 - PROVIDE A TIME CLOCK OR ASTRONOMICAL
 SWITCH TO TURN OFF DURING DAYLIGHT HOURS.
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE SIZES
  
  