| 2017-04-12 15:00:27 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040259 |
| | ADD: 500 N. CONGRESS AVE. |
| | CONT: PRO LINE BUILDERS |
| | TEL: 954-448-0298 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 12/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET, ARCHITECTURAL SHEETS AND SHEET S1 |
| | ALL INDICATE THE VULT WIND ZONE IS 160 MPH FOR A |
| | BUILDING WITH A RISK CATEGORY II. PLEASE NOTE THE 2014 |
| | FBC-B FIGURE 1609A PLACES US IN THE 170 MPH VULT WIND |
| | ZONE. NOTE # 2 DOES ALLOW FOR LINEAR INTERPOLATION |
| | BETWEEN CONTOURS IS PERMITTED. PLEASE ALSO NOTE THE |
| | PRESSURES ON SHEET S-1 WILL INCREASE FOR ALL ZONES. |
| | |
| | 2) THE PRODUCT APPROVALS THAT ARE INCORPORATED IN THE |
| | PLANS: |
| | PGT 1-4 FL331.3 FRENCH DOORS FD-555 |
| | TT 1-2 FL10537.1 THERMA TRU SINGLE IMPACT DOORS |
| | YKK 1-4 FL16314.2 FIXED WINDOWS YOW225 TUH |
| | NONE OF THESE APPROVALS IDENTIFY GLAZING, MULLIONS. |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 3) SHEET A-1 SHOWS THE NEW ELEVATOR SHAFT WALLS AND AN |
| | EXISTING STAIRWELL ADJACENT TO THE ELEVATOR. THE |
| | STAIRWELL SHOWS A NEW ROOM WITHIN THE STAIRWELL. FBC-B |
| | 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND RAMP |
| | OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR EXIT |
| | STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED EXTERIOR |
| | OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| | ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES |
| | AND FOR EGRESS FROM THE ENCLOSURE. |
| | |
| | 4) SHEET A1 SHOWS THE NEW LULA-ELEVATOR PLEASE PROVIDE |
| | THE MANUFACTURERS SPECIFICATION FOR COMPLIANCE WITH: |
| | WITH 408.1-4.8 ACCESSIBILITY CODE AND WITH ASME A17.1. |
| | |
| | 5) BUILDING PROVISO: SHEET A11 SHOWS WELDED CONNECTIONS |
| | BETWEEN THE STEEL POST AND OVERHEAD STEEL BEAMS W12X35 |
| | PLEASE SHOW COMPLIANCE WITH: |
| | WELDED OR BOLTED CONNECTIONS |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |